Removal and replacement procedures 56
3.
For each of the five clamps securing the sensor tube to the HP POD 40c G2 structure, remove the screw
that secures the clamp (1), rotate the clamp (2), and then pull the clamp out to remove the clamp (3).
4.
Remove the sensor tube.
Replacing the cold aisle temperature sensor
1.
Replace the sensor tube, and then secure the tube with five clamps. For each clamp, replace the clamp
(1), and then secure the clamp with a screw (2).
2.
Splice the two sensor tube wires with the red wires inside the sensor box.