• Extend the server from the rack (
Extend the server from the rack
on page 37).
• Remove the server from the rack (
Remove the server from the rack
on page 37.
4.
Remove the access panel (
on page 39).
5.
Remove all hot-plug hard drives (
on page 40).
6.
Remove the fan cage (
Removing and replacing the fan cage
7.
Disconnect all cables from the universal media bay.
8.
Remove the universal media bay.
To replace the component, reverse the removal procedure.
Removing and replacing the LFF power switch module
Procedure
1.
Power down the server (
on page 36).
2.
Remove all power:
a.
Disconnect each power cord from the power source.
b.
Disconnect each power cord from the server.
3.
Do one of the following:
• Extend the server from the rack (
Extend the server from the rack
on page 37).
• Remove the server from the rack (
Remove the server from the rack
on page 37).
4.
Remove the access panel (
on page 39).
5.
Remove all hot-plug hard drives (
on page 40).
6.
Remove the fan cage (
Removing and replacing the fan cage
7.
Disconnect all cables connecting the power switch module to the system board and other components.
8.
Feeding the cables through the front of the server, remove the power switch module.
54
Removing and replacing the LFF power switch module
Summary of Contents for ProLiant DL380
Page 31: ...Customer self repair 31 ...
Page 32: ...32 Customer self repair ...
Page 33: ...Customer self repair 33 ...
Page 34: ...34 Customer self repair ...
Page 106: ...106 Component identification ...
Page 117: ...Box 2 to SAS Expander All boxes Cabling 117 ...
Page 119: ...Box 2 Box 3 Cabling 119 ...