DTU  connects  the  power  production  of  each  microinverter.  If  the  asymmetry  current  is  going  to 

exceed 16 A, DTU will send stop signal to one or more microinverters to let the asymmetry current 

lower than 16A. 

 

 

Each branch should provide a 20A circuit breaker, but no need for central protection unit. 

 

 

8. Decommissions 

8.1 Decommissions 

Disconnect the inverter from DC input and AC output; remove all connection cable from the 
Microinverter; remove the Microinverter from the frame.   

Please pack the Microinverter with the original packaging, or use the carton box that can afford 5kg 
weight and can be fully closed if the original packaging is no longer available. 

 

8.2 Storage and Transportation 

Hoymiles packages and protects individual components using suitable means to make the transport 
and subsequent handling easier. Transportation of the equipment, especially by road, must be carried 
out  by  suitable  ways  for  protecting  the  components  (in  particular,  the  electronic  components) from 
violent, shocks, humidity, vibration, etc. Please dispose the packaging elements in appropriate ways 
to avoid unforeseen injury. 

It  is  the  customer’s  responsibility  to  examine  the  condition  of  the  components  transported.  Once 
receiving the Microinverter, it is necessary to check the container for any external damage and verify 
receipt  of  all  items.  Call  the  delivering  carrier  immediately  if  damage  or  shortage  is  detected.  If 
inspection  reveals  damage  to  the  inverter,  contact  the  supplier,  or  authorized  distributor  for  a 
repair/return determination and instructions regarding the process.   

The microinverter storage temperature is -40-85

.   

 

8.3 Disposal 

If the equipment is not used immediately or is stored for long periods, check that it is correctly 
packed.  The  equipment  must  be  stored  in  well-ventilated  indoor  areas  that  do  not  have 
characteristics that might damage the components of the equipment. 

Summary of Contents for MI-500

Page 1: ...Version B1 0 2019...

Page 2: ...control the production of a single photovoltaic module directly consequently improving the flexibility and reliability of the system About the manual This manual contains important instructions for t...

Page 3: ...Introduction 8 3 4 Dimension 9 4 About Function 9 4 1 Work Mode 9 5 About Installation 10 5 1 Accessories 10 5 2 Installation Precaution 11 5 3 Space Distance Required 11 5 4 Preparation 12 5 5 Instal...

Page 4: ...2019 Hoymiles Converter Technology Co Ltd All rights reserved 4 MI 500 MI 600 MI 700 9 2 AC Output 21 9 3 Efficiency Safety and Protection 22 9 4 General Data 22...

Page 5: ...nstall and maintain this Microinverter under the guide of this document for safety purpose 1 3Symbols Used The safety symbols in this user manual are show as below Symbol Usage Indicates a hazardous s...

Page 6: ...photo voltaic module can be connected to one input of the inverter Do not connect batteries or other sources of power supply The inverter can be used only if all the technical characteristics are obse...

Page 7: ...in operation Danger of high voltages Danger to life due to high voltage in the microinverter Beware of hot surface The inverter can become hot during operation Avoid contact with metal surfaces durin...

Page 8: ...700W Adapted to 60 72 cells PV panels Peak efficiency 96 70 CEC weighted efficiency 96 50 Static MPPT efficiency 99 80 Dynamic MPPT efficiency 99 76 in overcast weather High reliability NEMA6 IP67 en...

Page 9: ...feed in to Public Grid Zero Export Control Under this mode Microinverter s generation is limit base on the current house loads there will be no extra power feed in to the Public Grid Stand by There a...

Page 10: ...nal please contact our sales to purchase base on the quantity required on actual installation Object Description A AC Extension Cable B AC End Cable Female 2m 12 AWG cable C AC Female Connector D AC M...

Page 11: ...ons under the PV module to avoiding direct sunlight rain exposure snow layup UV etc Note For some countries the DTU will be required to meet the local grid regulation e g G98 99 for UK 5 3 Space Dista...

Page 12: ...ng due to an increase in the microinverter internal temperature do not expose it to direct sunlight To avoid overheating always make sure the air flow around the inverter is not blocked Do not install...

Page 13: ...bserve the certification documents concerning the maximum number of Micro inverters permitted for installation at each cable section The Microinverter must be under the module out of long term exposur...

Page 14: ...icroinverter s AC Male connector B Connect the other side of the AC End Cable to the distribution box and wire it to the local grid network Close the distribution box after the wiring is completed Not...

Page 15: ...e PV modules above the microinverters B Connect the PV modules DC cables to the DC input side of the microinverter The recommended installation need to keep the Microinverter underneath the photovolta...

Page 16: ...lease contact your installer to check the AC wiring 04 Please Contact your installer and provide Panel specs 05 Please contact your installer to check the DC side installation and PV configuration 06...

Page 17: ...the in appendix Technical Data of this microinverter 2 Check the connection to the utility grid Verify utility power is present at the inverter in question by removing AC then DC power Never disconnec...

Page 18: ...e fault removed Conduct an annual inspection on various components and clean the equipment with a vacuum cleaner or special brushes Do not attempt to dismantle the Microinverter or make any internal r...

Page 19: ...2019 Hoymiles Converter Technology Co Ltd All rights reserved 19 MI 500 MI 600 MI 700 7 Sample Wiring Diagram Fig 2 Single Phase Wiring Diagram Fig 3 Three phase wiring diagram...

Page 20: ...quent handling easier Transportation of the equipment especially by road must be carried out by suitable ways for protecting the components in particular the electronic components from violent shocks...

Page 21: ...mum input voltage V 60 60 60 Maximum input current A 10 5 11 5 11 5 Model MI 500 MI 600 MI 700 Rated output power W 500 600 700 Rated output current A 2 17 230V a c 2 08 240V a c 2 40 208V a c 2 27 22...

Page 22: ...y 96 50 96 50 96 50 Nominal MPPT efficiency 99 80 99 80 99 80 Night time power consumption mW 50 50 50 Model MI 500 MI 600 MI 700 Ambient temperature range 40 65 40 65 40 65 Operating temperature rang...

Page 23: ...2019 Hoymiles Converter Technology Co Ltd All rights reserved 23 MI 500 MI 600 MI 700 Appendix 1 Installation Map...

Reviews: