INSTAllATION
2.
Installation
2.1
Set-up
!
WARNING
The boiler must only be suspended using the four points marked as the crane suspension option in Fig.
02. The hooks on the back of the boiler must
not
be used to suspend it.
Space requirement of UltraGas
®
(1550)
(All dimensions in mm)
If the gas line is routed
horizontally
to the
left
, the minimum distance D
must be observed.
For swinging out the burner,
this area must remain free
(see dimension table)
Fig. 01
UltraGas
®
Type
A
A minimum
B
C
D
H
H minimum
(1550)
-
450
1
1550
2
2090
200
2560
2455
3
1
If the room height is too low, the dimension can be reduced. See A minimum.
2
Caution! At A minimum, the burner can no longer be swivelled out completely! Cleaning is made difficult!
3
Feet can be shortened, no pedestal casing possible! For details see next page.
• The boiler can be placed with one side directly on the wall. For the casing to be installed, however, there
must be a distance of at least 100 mm from the wall.
• The cleaning opening must be easily accessible. A minimum distance of 500 mm must be maintained on
the cleaning opening side (*) for this purpose.