3.5
Boiler-Flow resistance
UltraGas
®
(15-27)
UltraGas
®
(35,50)
0
5
10
15
20
25
30
0
0,5
1
1,5
2
2,5
3
3,5
4
4,5
5
[m
3
/h]
[mbar]
0
5
10
15
20
25
30
35
0
1
2
3
[m3/h]
[mbar]
3.6
Brief description of the
automatic firing device
The automatic firing device BIC960 of the UltraGas
®
only
operates in conjunction with the heating controller Top-
Tronic
®
E/UG. For this reason, the automatic firing device
only needs to take care of the last remaining functions to
ensure the correct operation of a modulating gas boiler.
The automatic firing device comprises the following func
-
tions:
•
PWM fan control (230V AC)
•
Modulating operation
•
Common electrode for ignition and flame monitoring
(ionisation)
• LPG valve and boiler room fan controllable
• Inputs for
-
flow sensor 1
-
flow sensor 2
-
flue gas sensor
- water pressure sensor
- safety temperature limiter (not used)
- air pressure switch
- gas pressure switch
•
Status outputs «fault» and «flame signal»
• Allows connection of additional (external) ignition device
•
RS 485 connection to TopTronic
®
E/UG
•
RS 232 connection to PC
•
Start attempts: maximum 4
•
Safety period: 5 sec
•
Pre-ignition period: 5 sec
•
Pre-purging period: 50 sec
•
Follow-on time pump (230V AC): 5 min after heat demand
Sicherungen:
The BIC 960 is fitted with 3 fuses:
2AT
Mains
4AT
Pump
4AT
Burner fan
Blowing of one of the two 4AT fuses securing the pump
or the burner fan, respectively, will prevent the affected
device from starting.
A failure of the mains fuse of the automatic firing device is
displayed on the TopTronic
®
E/UG by the failure message
„B:30 Bus interruption to automatic device“. The failure
appears when there is no communication between auto-
matic firing device and TopTronic
®
E/UG.
m
3
/h = Volume flow
mbar = Flow resistance
12
4 217 213 / 01
TECHNICAL INFORMATION