4 213 321 V01 KDT RegelModul Solar EN.docx
79 / 95
0
80
60
40
20
100
PS1 on
VK
TxU
TKR
TKOmin
TKV
TKO
TKOref
nPS1
ΔT 10K
DIFF on (08-001)
VK max
ΔT 20K
DIFF (08-064)
ΔT 5K
DIFF off (08-002)
Parameter:
08-108 Option collector flow sensor
Output:
00-060 Collector flow temperature TKVx
12.8.2. Menu: Collector
– TKV
Parameters Designation
Value
Min. Max. Comments
R W
08-108
TKV collector flow
option
0
0
1
Option TKV collector flow sensor. This can
be connected as an additional measuring
point and is then used as a reference sensor
for speed control of the solar charging.
3
3
30-018
Alloc TKV coll.
flow temp. input
0=OFF
Allocation input (VE1, VE2, VE3/IMP,
VE1/FE-1, etc.)
3
3
Charging plausibility:
If the TKV option collector flow sensor (08-108) and flow sensor (08-107) options are active, the collector flow and
return are registered by temperature sensors.
The temperature difference between these two values is measured. If this difference is 2 on average, charging is
completed because no sensible charging of the consumer can take place any longer.
Also, the difference between collector sensor TKO and collector flow TKV is monitored. An excessive drifting
apart of these values should be avoided.
If the collector maximum temperature on the TKO (08-011) is reached less 20 K, the minimum speed (08-035) is
increased continuously as the temperature rises. In this way, the temperature at the collector should be forced to
be dissipated.
nmin = (08-035), if TKO < TKmax (08-011) - 20 K
nmax = (08-036), if TKO > TKmax (08-011)