11.16.1. High-temperature discharge storage tank option
1 =
High-temperature discharge storage tank
If the temperature at "storage tank sensor top" TxO is higher than the maximum storage tank temperature Txmax
(08-059), output HTE is switched to storage tank temperature discharge / mandatory energy dissipation. In this
case, the temperature can be dissipated by a hot air blower or a radiator, for example. The function is only ever
active on that storage tank for which the option was selected.
If the maximum storage tank temperature Txmax (08-059) on the storage tank sensor top TxO is undershot by 5K,
the mandatory energy dissipation procedure is terminated.
HTE on if T1O > T1max (08-059)
HTE off if T1O < T1max (08-059)
– 5K
40
50
60
70
80
90
100
110
HTE on
DISCH off
T1O
PS1 on
TKO
T1max
(08-059)
T1max (08-059)
– 5K
HT relief on
PS1 on