11.13. Charging with plate heat exchanger
In the TTE Sol, there is a differentiation between charging with a central plate heat exchanger and a
decentralised one.
Central plate exchanger:
Here, all consumers are charged in one system by means of one central plate exchanger. (Standard hydraulics in
control module TTE-SOL)
Decentralised plate exchanger:
The plate exchanger is a decentralised one if one consumer must be charged without its own system separation.
(E.g. swimming pool or heating buffer tank without coil)
11.14. PWTz (central plate heat exchanger)
Charging all consumers via a central plate heat exchanger. When the PWTz pump (central heat exchanger pump)
starts, it runs for 5s at 100% to overcome the break-loose torque. This guarantees correct starting.
When the solar pump is active, the central plate heat exchanger pump runs at the set minimum speed of rotation
(08-025) until the charging reference value on the TWVz (central heat exchanger flow temperature) sensor is
reached. The controller now attempts to maintain the charging reference value on the central heat exchanger flow
temperature sensor by controlling the speed of rotation. The charging reference value depends on the selected
charging strategy (yield or reference, as well as combination of the two). If the temperature difference TKO… to
TxU is less than the "Increase off", the pumps switch off.
11.14.1. Menu: General PWTZ (pump heat exchanger central)
Parameters
Designation
Value Min.
Max.
Comments
R
W
30-004
Alloc. TWVz - heat
exchanger input
cent.
0=OFF
Allocation input for TWV - central heat exchanger
temperature
0=OFF, 1=VE1, 2=VE2, 3=VE3, 5=FVT-T,
7=VE1-FE1, 8=VE2-FE1, 9=VE3-FE1, 11=FVT-
T-FE1, 13=VE1-FE2, 14=VE2-FE2, 15=VE3-
FE2, 17=FVT-T-FE2
4 4
32-013
Alloc. PWM output
PWTz WT pump
central
0=OFF
Allocation of the output (VA10/PWM, VA10/PWM
on FE-1, etc.)
4 4
08-025
Min. PWTz speed
WT pump decentral
30%
5
100
Minimum speed of rotation of the secondary pump,
on charging via an external heat exchanger.
4 4
28-003
Min. downtime
PWTz pmp. WT
centr.
10 sec
0
200
Off-period for the output. After switching off,
the output is blocked for this time to prevent
reactivation. Parameter for high efficiency or
electronic pumps (relay protection function).
4 4