4 213 321 V01 KDT RegelModul Solar EN.docx
43 / 95
100
50
%
V
10
5
0
0
{X
1
,Y
1
}
{X
2
,Y
2
}
x
y
The characteristic can also have a negative slope. In this case, the switch-off voltage is not considered.
11.12.1. Menu: General 0-10V/PWM
Parameters
Designation
Value
Min.
Max.
Comments
R
W
33-100
Configuration 0-10 V/PWM
2
0
3
Configuration 0-10V/PWM
output 1
0=OFF
1=0-10V
2=PWM (0%=0V)
3=PWM inverted (0%=10V)
3 3
20-038
Characteristic curve 1 (X1)
0 %/°C
0.0
100.0
4 4
20-039
Characteristic curve 1 vltg. (Y1)
at X1
0 V
0.0
10.0
4 4
20-040
Characteristic curve 1 (X2)
100 %/°C
0.0
100.0
4 4
20-041
Characteristic curve 1 vltg. (Y2)
at X2
10 V
0.0
10.0
4 4
20-054
Char. curve 1 switch-off voltage
0 V
0.0
10.0
5 5
33-101
Configuration 0-10V/PWM - FE 1
2
0
3
Configuration 0-10V/PWM
output 1
0=OFF
1=0-10V
2=PWM (0%=0V)
3=PWM inverted (0%=10V)
3 3
20-042
Characteristic curve 2 (X1)
0 %/°C
0.0
100.0
4 4
20-043
Characteristic curve 2 vltg. (Y1)
at X1
0 V
0.0
10.0
4 4
20-044
Characteristic curve 2 (X2)
100 %/°C
0.0
100.0
4 4
20-045
Characteristic curve 2 vltg. (Y2)
at X2
10 V
0.0
10.0
4 4
20-055
Char. curve 2 switch-off voltage
0 V
0.0
10.0
5 5