11.10. Thermostat function
Three thermostat functions can be activated in the controller. The description below relates to the first thermostat
function.
A thermostat function is activated by allocating the thermostat output THA1 and thermostat sensor THF1.
The thermostat output is switched on if the temperature drops below the reference value less half the differential
gap, and is switched off if the sensor temperature rises above the reference value plus half the differential gap.
The function starts switched-off when the controller is restarted.
11.10.1. General thermostat menu
Parameters
Designation
Value
Min.
Max.
Comments
R
W
32-028
Alloc. outp. THA1 -
thermostat 1
0=OFF
Allocation output THA1 - thermostat 1:
0=OFF, 1=VA1, 2=VA2, 3=VA3, 9=VA1-FE1,
10=VA2-FE1, 11=VA3-FE1, 13=VA1-FE2,
14=VA2-FE2, 15=VA3-FE2
4 4
30-036
Alloc. inp. THF1 -
thermostat sensor 1
0=OFF
Allocation input THF1 - thermostat sensor 1:
0=OFF, 1=VE1, 2=VE2, 3=VE3, 5=FVT-T,
7=VE1-FE1, 8=VE2-FE1, 9=VE3-FE1,
11=FVT-T-FE1, 13=VE1-FE2, 14=VE2-FE2,
15=VE3-FE2, 17=FVT-T-FE2
4 4
29-060
THF1 ref. thermostat
sensor 1
0 °C
-
20.0
250.0
THF1 ref. thermostat sensor 1
4 4
29-063
Thermostat 1
switching difference
3 K
1.0
90.0
Thermostat 1 switching difference
4 4
32-029
Alloc. outp. THA2 -
thermostat 2
0=OFF
Allocation output THA2 - thermostat 2:
0=OFF, 1=VA1, 2=VA2, 3=VA3, 9=VA1-FE1,
10=VA2-FE1, 11=VA3-FE1, 13=VA1-FE2,
14=VA2-FE2, 15=VA3-FE2
4 4
30-037
Alloc. inp. THF2 -
thermostat sensor 2
0=OFF
Allocation input THF2 - thermostat sensor2:
0=OFF, 1=VE1, 2=VE2, 3=VE3, 5=FVT-T,
7=VE1-FE1, 8=VE2-FE1, 9=VE3-FE1,
11=FVT-T-FE1, 13=VE1-FE2, 14=VE2-FE2,
15=VE3-FE2, 17=FVT-T-FE2
4 4
29-061
THF2 ref. thermostat
sensor 2
0 °C
-
20.0
250.0
THF2 ref. thermostat sensor 2
4 4
29-064
Thermostat 2
switching difference
3 K
1.0
90.0
Thermostat 2 switching difference
4 4
32-030
Alloc. outp. THA3 -
thermostat 3
0=OFF
Allocation output THA3 - thermostat 3:
0=OFF, 1=VA1, 2=VA2, 3=VA3, 9=VA1-FE1,
10=VA2-FE1, 11=VA3-FE1, 13=VA1-FE2,
14=VA2-FE2, 15=VA3-FE2
4 4
30-038
Alloc. inp. THF3 -
thermostat sensor 3
0=OFF
Allocation input THF3 - thermostat sensor3:
0=OFF, 1=VE1, 2=VE2, 3=VE3, 5=FVT-T,
7=VE1-FE1, 8=VE2-FE1, 9=VE3-FE1,
11=FVT-T-FE1, 13=VE1-FE2, 14=VE2-FE2,
15=VE3-FE2, 17=FVT-T-FE2
4 4
29-062
THF3 ref. thermostat
sensor 3
0 °C
-
20.0
250.0
THF3 ref. thermostat sensor 3
4 4
29-065
Thermostat 3
switching difference
3 K
1.0
90.0
Thermostat 3 switching difference
4 4