6.
Basic settings
6.1.
Access levels / code input
The TopTronic® E control system provides different access levels. The codes are entered in the main menu
–
"User Level" menu item.
Levels (code):
Operator code: No code
Technical operator code: ………….….
Specialist
code: ………………………………
OEM code: ……………………………………….
6.2.
Hydraulic applications
To facilitate setting and commissioning of the TopTronic® E control system, predefined hydraulic applications can
be selected in each module. Selecting the corresponding hydraulics sets very many parameters to the correct
value. At the same time, this defines the input/output allocations of the functions. If a hydraulic application is
adjusted, this means the parameters in the individual functions are reset to their factory setting at the same time.
Consequently, during commissioning of the control system, always set the hydraulic application first.
The hydraulic application is set in the menu: General
– General – Configuration – Par. 4006
6.3.
Hydraulic options
In addition to the hydraulic applications, there are additional options that can be activated depending on the
selected hydraulic application.
The settings for these options are described in the particular chapters at the point where the options are also
located in the menu structure.