6 Operating menu zone
Precondition: The
User
operator level is active (password entry see section 2.6).
■
Navigate to the next page with .
Operating menu 01/05
ZONE
REMU Operating mode:
7
1=ST/2=SA1/3=SA2
4=REC1/5=REC/6=EXT
7=AUTO
10:18 28.07.17
Selecting the operating mode:
■
Navigate to the input field with
.
■
Set the desired operating mode with .
■
Confirm with
.
Operating menu 02/05
ZONE
Room temp. setpoints:
Day
21.0
Cool prot. 15.0
Overheat prot. 27.0
10:18 28.07.17
Setting room temperature setpoints –
Day / Cooling protection / Overheating
protection:
■
Navigate to the input field with
.
■
Set value with .
■
Confirm with
.
Operating menu 03/05
ZONE
Night cooling summer
0
0=Off/1=Auto
Room setpoint 21.0
Fan setpoint 100%
(only valid for REMU)
10:18 28.07.17
Setting night cooling – Enabling, Room
setpoint and Fan setpoint:
■
Navigate to the input field with
.
■
Set value with .
■
Confirm with
.
Operating menu 04/05
ZONE
Runtime
Button ST
30min
Button REC 30min
Fresh air rate 10.0%
10:18 28.07.17
Setting the runtime of the operating selector
buttons:
■
Navigate to the button with .
■
Set value with .
■
Confirm with
.
When a button is activated the units switch
back to automatic mode after this runtime.
Setting the fresh air rate:
■
Navigate to the input field with
.
■
Set value with .
■
Confirm with
.
(only for supply air units)
Operating menu 05/05
ZONE
Room air
temperature alarms
Min limit < 5.0
Max limit > 40.0
10:18 28.07.17
Setting the lower and upper limits of room
temperature:
■
Navigate to the limit with .
■
Set value with .
■
Confirm with
.
An alarm is triggered if the room air
temperature is outsides these limits.
18
TopTronic
®
C
System control for TopVent
®
Operating menu zone
4 216 689-en-01