Alarm/fault display

6.1 

Types of error

There are 3 types of message (see below). Three different 

messages can be shown on the display at the same time.

Press  the  setting  knob  on  the  control  panel  once  to 

acknowledge and reset the message.

•  The 

information message 

does not affect the function 

of  the  calorifier/heat  pump;  however,  it  notifies  the 

user of a problem that should be remedied as soon as 

possible (message 8, 9 and 10).

• 

In  the  event  of 

refrigerant circuit error messages

the supply of hot water by the heat pump is interrupted. 

If the electrical additional heating is activated, this takes 

over  the  hot  water  supply  until  the  target  hot  water 

temperature is reached (error message 3, 4, 5 and 6).

• 

In the event of 

error messages for the overall system

the  hot  water  supply  is  stopped  completely.  These 

messages  are  most  likely  due  to  a  sensor  error  (error 

message 1 and 2).

The  user  can  view  the  error  messages  in  the  display. 

The error messages are acknowledged by pressing the 

setting  knob.  Before  the  calorifier/heat  pump  returns 

to  normal  operation,  the  error  must  be  rectified  and 

acknowledged.  If  the  error  is  not  rectified,  the  error 

message  will  remain  on  the  display.  If  several  error 

messages occur at the same time, these will be shown 

in the second line of the display, listed in order of priority.

The pressure switch error messages 5 & 6 are dealt with 

as follows.

Error message 5 (pressure switch error message appearing 

for the first time): the heat pump is switched off. The heat 

pump  starts  up  again  if  the  pressure  normalises  of  its 

own accord. In the case of error message 5, the indicator 

LED  (1)  flashes  red.  As  soon  as  the  error  is  rectified 

(or  has  resolved  itself),  the  indicator  LED  automatically 

changes  to  orange  (flashing).  After  the  error  message 

has been acknowledged, the indicator LED then indicates 

the operating or standby mode of the calorifier/heat pump 

(= indicator LED permanently green or orange). 

If the same error occurs again within 6 hours of the first 

error message, error message 6 is displayed. The heat 

pump  is  switched  off.  The  HP  can  only  start  up  again 

after the error has been rectified and the error message 

has been acknowledged. In the case of error message 6, 

the indicator LED (1) flashes red. As soon as the error 

is  rectified,  and  once  the  error  message  has  been 

acknowledged by pressing the setting knob, the calorifier/

heat  pump  then  changes  to  the  operating  or  standby 

mode (= indicator LED permanently green or orange).

Indicator LED: error messages

The indicator LED (1) of the heat pump is flashing red: 

Error  message  for  the  refrigerant  circuit  or  information 

message. Both indicator LEDs (1 + 2) flashing: storage 

tank sensor faulty, it is not possible to heat up the water.

1.  Operating and fault indicator, 

heat pump.

 

Flashing red = fault in alarm 

group 2 or 3

2.  Operating and fault indicator, 

additional heating (boiler or 

electric heating element).

Both indicators (1 + 2) flashing red =

fault in alarm group 1

3.  Display

 

Alarm

  9    0    0

Acknowledge =

 

press switch

Control panel

1 2 3

4

6.2 

Overview of error messages

Error

number

Indicator LED

Cause of error

Effect

No. 1

No. 2

1

flashing (red) flashing (red) Short circuit on temperature sensor 

in upper region of storage tank

Heat pump and additional heating 

switched off.

2

flashing (red) flashing (red) Temperature sensor in upper region 

of storage tank disconnected.

Heat pump and additional heating 

switched off.

3

flashing (red)

Short circuit on temperature sensor 

on the evaporator.

Compressor is switched off.

10

4 215 949 / 00

ALArM/FAULT DISPLAy

Summary of Contents for CombiVal WPE

Page 1: ...67 27 11 Fax 44 1636 67 35 32 Export Hoval Aktiengesellschaft Austrasse 70 LI 9490 Vaduz Principality of Liechtenstein Phone 423 399 24 00 Fax 423 399 24 11 Subject to modifications EN Operating Instructions CombiVal WPE 300 WPER 300 WPEF 300 Calorifier heat pump 4 215 949 00 02 18 ...

Page 2: ...ionella 9 6 Alarm fault display 10 6 1 Types of error 10 6 2 Overview of error messages 10 7 Fault determination 11 8 Operation maintenance service 13 8 1 Operation and maintenance 13 8 2 General checks 13 8 3 Magnesium protection anode 13 8 4 Cleaning the air duct 13 8 5 Service 13 Heating installer Tel no Heating plumber Tel no Electrical installer Tel no 1 Important addresses 2 4 215 949 00 INH...

Page 3: ... designed and for which it has been approved by Hoval Do not make any modifications to the unit as this will invalidate any legal claims Conversion kits must be installed and approved by the licensed installer or Hoval Customer Service In the event of a fault or damage please contact Hoval Customer Service to inquire about the necessary repairs It is essential to shut down the unit to prevent dama...

Page 4: ...ith a diameter of 160 mm Large air intake with a diameter of 160 mm Electric heating element Double enamelled calorifier Magnesium protection anode Thermal insulation made from polyurethane Condenser on the outside of the steel casing of the calorifier prevents limescale formation Fully hermetic piston compressor Easy microprocessor control panel with control knob display operating and warning lig...

Page 5: ...s at the bottom The display is activated by turning or pressing the program switch 4 the display will light up Control switch Turning Select value set values Pressing Change confirm 1 Press and release a flashing line number will appear setting can be changed If the change is not acknowledged press again briefly it will not take effect 2 Press and hold 3 sec switch to service menu 4 1 User level m...

Page 6: ... Press the switch acknowledge the new set temperature is now in effect The setting should be between 45 C and 55 C 6 Min hot water temperature T min 35 C Target minimum temperature This is set in the same way see point 5 hot water temperature If the temperature falls below this value the additional heating selected in the operating mode point 8 will be switched on 7 Min hot water temperature T2 mi...

Page 7: ...d for a period of time longer than this the function must be reprogrammed 12 Configuring separate fan FanConf 1 Mode display This function is intended for separate ventilation with the fan when the heat pump is in standby mode 1 Fan speed 1 lower quantity of air 2 Fan speed 2 greater quantity of air 0 No separate ventilation function for the fan Fan only to be used when heat pump in operation 13 F...

Page 8: ...ence function Holiday OFF OFF 1 week 2 weeks 3 weeks 3 days Manual see also point 18 Deactivation activation of the absence function and of the min HW temperature T2 min 18 Days absent DaysAbs 1 1 99 Individual specification of days absent if Manual was selected under point 17 The HW temperature can be reduced as low as T2 min 19 Remaining days absent Days 0 0 99 Display of the remaining days abse...

Page 9: ...hen the temperature falls below the evaporation temperature of 18 C The operating status is displayed on the control panel See page 5 display 3 5 2 Defrost mode Defrost mode hot gas bypass activates automatically when required Defrosting using the defrost valve is initiated fan off when the temperature at the evaporator is 2 C Defrosting ends when the temperature at the defrost sensor reaches a va...

Page 10: ... or has resolved itself the indicator LED automatically changes to orange flashing After the error message has been acknowledged the indicator LED then indicates the operating or standby mode of the calorifier heat pump indicator LED permanently green or orange If the same error occurs again within 6 hours of the first error message error message 6 is displayed The heat pump is switched off The HP...

Page 11: ... maintenance contract Should something goes wrong despite this go through the fault checklist below Make sure that you have complied with the instructions in the manual If you are unable to rectify the fault with the aid of the checklist please contact Hoval Customer Service Type CombiVal WPE WPER Fault Cause Remedy Alarm message in display See error display See error display Electrical fault No d...

Page 12: ...PE WPER Fault Cause Remedy Discharge of condensate during operation Condensate drain blocked Clean Odour No drain trap fitted No water in drain trap Install drain trap Top up water 12 4 215 949 00 Alarm fault display ...

Page 13: ...ing and the area around the unit clean Wipe the installation regularly with a damp cloth to remove dust and contamination In this way leakage points are identified sooner and can be repaired From time to time check that all connections are secure From time to time check that the operating voltage and phase unbalance are still within the specified limits Performance checks The temperature differenc...

Page 14: ...9 www hoval ch Germany Hoval GmbH Humboldtstrasse 30 DE 85609 Aschheim Dornach Phone 49 89 92 20 97 0 Fax 49 89 92 20 97 77 www hoval de Austria Hoval Gesellschaft mbH Hovalstrasse 11 AT 4614 Marchtrenk Phone 43 50 365 0 Fax 43 50 365 5005 www hoval at Italy Hoval s r l Via XXV Aprile 1945 13 15 IT 24050 Zanica BG Phone 39 035 666 1111 Fax 39 035 526 959 www hoval it France Hoval SAS Parc d Activi...

Reviews: