8.3
Safety temperature limiter - Reset
If the boiler temperature rises too high (>100 °C), the system is switched off by the safety temperature limiter (STL)
by means of a mechanical lockout.
The malfunction must first be unlocked on the safety temperature limiter, then on the control panel (with reset button).
2. Fault reset on the control panel
1. STL reset
Fig. 42
3. Open the electrical box
4. Unscrew the protective cap
5. Reset the STL
6. Open the cover
7. Press the reset button
Press the reset button on the control: the boiler is ready for operation again once the boiler water temperature is less
than 80 °C.
50