7
4 220 456 / 02
INSTAllATION
2.
Installation
2.1
Set-up
!
WARNING
The boiler must only be suspended using the four points marked as the crane suspension option in Fig. 02.
The hooks on the rear of the boiler must
not
be used to suspend it.
If the gas line is routed horizontally to the left,
the minimum distance Q must be observed.
For swinging out the burner, this area must
remain free (see dimension table)
2.1.1 Space requirement of UltraGas
®
2 (125-1550)
(Dimensions in mm)
Fig. 01
Type
A
1)
A minimum
2)
B
C
H
3)
H minimum
4)
Q
UltraGas
®
2 (125,150)
169
106
720
1060
2053
1933
125
UltraGas
®
2 (190,230)
155
71
820
1160
2098
1978
2
UltraGas
®
2 (300,350)
285
170
930
1510
2158
2038
65
UltraGas
®
2 (400,450)
230
157
930
1510
2228
2108
141
UltraGas
®
2 (530-700)
121
121
1110
1600
2364
2244
155
UltraGas
®
2 (800-1100)
280
195
1290
1786
2385
2265
119
UltraGas
®
2 (1300,1550)
291
154
1560
2104
2525
2405
163
1)
If the room height is too low: the dimension A can be reduced.
2)
Caution!
At A minimum, the burner can no longer be swivelled out completely! Cleaning is made difficult!
3)
Height value assumes adjustable feet are set to 30 mm
4)
The feet can be shortened.
Caution!
If the feet are shortened, the base strip cannot be installed and the installer will have to fit a siphon with min.
70 mm barrier height. For details see next page.
* The boiler can be placed with one side directly on the wall. However, to protect heat-sensitive walls
against damage, a distance of at least 150 mm from the wall must be provided.
* The cleaning opening must be easily accessible. As a result, a minimum distance of 500 mm must be
maintained on the cleaning opening side.