4.5
TROUBLESHOOTING
SYMPTOM
POSSIBLE CAUSES
SOLUTION
System fault
Pump not primed properly
Bleed all trapped air from lines. Restart system.
Isolation valves may be closed
Open valves. Restart system.
Hose kinked or crushed
Remove obstruction. Restart system.
Leak in suction line
Repair leak. Bleed and restart system.
Pump motor turning
backwards
Reverse any two power leads (in three-phase system).
Restart system.
See
systems, contact Hotstart.
Control TCR failure: closed
Check and replace if necessary.
See
SECTION 4.2.10
Motor failure
Check and replace if necessary. Restart system.
Motor contactor failure
Disconnect system power and check contactor. Replace if
needed.
See
Motor protection switch
tripped
Check and reset switch. If problem occurs again, check
motor. Restart system.
See
SECTION 4.1
RTD failure
Check TCR and RTD. See
SECTION 4.2.10
.
RTD cable failure
Check TCR and RTD. See
SECTION 4.2.10
.
Fluid temperature
too low
Motor failure
Check motor. Replace if necessary.
Heating system has been
turned off and fluid is cold
Allow time for the heating system to heat fluid.
Heating element failed
Check elements for continuity. Replace element if
necessary.
Element contactor failed
Check contacts and coil. Replace if necessary.
Motor contactor failed
Check contacts and coil. Replace if necessary.
Control TCR failure: open
Check and replace if necessary.
See
SECTION 4.2.10
Control TCR set point too low
Adjust set point for control TCR.
See
SECTION 3.2.3.
RTD failure
Check TCR and RTD. See
SECTION 4.2.10
RTD cable failure
Check TCR and RTD. See
SECTION 4.2.10
.