background image

MAN1197-02-EN

Indianapolis, USA  |  Cork, Ireland  |  Calgary, Canada  |  Bangalore, India  |  Oakleigh, Australia  |  Tianjin, China  |  Esteio, Brazil

Please visit our website for a complete listing and to learn more about certified Horner Automation products.
This document is the property of Horner Automation Group, and is subject to change. 

EXL10 OCS QUICK REFERENCE GUIDE

page 1 of 4

General Specifications

EXL10 Overview

3

4 5 6

7

8
9

10

11

12

13

14

15

1

2

1. Touchscreen
2. Function Keys
3. Audio Out/In
4. USB 2.0 ‘A’: Flash Storage
5. LAN1 Port
6. LAN2 Port
7.  Built-In I/O
8.  MJ1/MJ2: RS-232
     & 1/2 Duplex RS-485
9. Dip Switches
10. MJ3: RS-232/485
11. CAN1: Can I/O & Fieldbus Port
12. Power: 10-30VDC In
13. microSD: Data Storage
14. USB mini ‘B’: Programming
15. CAN 2: CAN I/O

Required Power (Steady State) 650mA @ 24VDC

Required Power (Inrush) 

25A for 

< 1

ms @ 24VDC, DC switched

Primary Power Range

10 - 30VDC

Relative Humidity

5 to 95% non-condensing

Typical Power Backlight 100%

12.432W @ 24VDC

Power Backlight 50%

9.312W @ 24VDC

Power Backlight OFF

6.048W @ 24VDC

Clock Accuracy

 + / - 20 ppm maximum at 25°C  
(+/- 1 min/month)

Real Time Clock

Battery Backed, Rechargeable Lithium

Operating Air Temp

-10°C to +60°C 

Storage Temp

-20°C to +60°C

Weight (without I/O)

3.9375 lbs (1786g)

Altitude

Up to 2000m

Rated Pollution Degree

Evaluated for Pollution Degree 2 Rating

Certifications  
(UL/CE)

North America:   

 

https://hornerautomation.com/certifications/ 

Europe: 
 

http://www.horner-apg.com/en/support/certification.

asp

x

NOTE:

 See Precaution #12 on page 4 about USB and grounding. 

Summary of Contents for EXL10

Page 1: ...Port 12 Power 10 30VDC In 13 microSD Data Storage 14 USB mini B Programming 15 CAN 2 CAN I O Required Power Steady State 650mA 24VDC Required Power Inrush 25A for 1ms 24VDC DC switched Primary Power Range 10 30VDC Relative Humidity 5 to 95 non condensing Typical Power Backlight 100 12 432W 24VDC Power Backlight 50 9 312W 24VDC Power Backlight OFF 6 048W 24VDC Clock Accuracy 20 ppm maximum at 25 C ...

Page 2: ...4 Q3 OUT 3 Q2 OUT2 PWM2 Q1 OUT1 PWM1 MODEL 3 12 DC In 12 DC Out 2 12 bit Analog In J1 Orange Digital Analog In I1 IN1 I2 IN2 I3 IN3 I4 IN4 I5 IN5 I6 IN6 I7 IN7 I8 IN8 H1 HSC1 IN9 H2 HSC2 IN10 H3 HSC3 IN11 H4 HSC4 IN12 A1 Analog IN1 A2 Analog IN2 0V Common 0 10VDC LOOP PWR 20mA I1 I2 I3 I4 I5 I6 I7 I8 H1 H2 H3 H4 A1 A2 OV 12 24VDC OV V Q13 Q12 Q11 Q10 Q9 Q8 Q7 Q6 Q5 Q4 Q3 Q2 Q1 LOAD LOAD LOAD LOAD ...

Page 3: ... V IN10 H3 HSC3 V IN11 H4 HSC4 V IN12 J1B 0V Common A1A Univ AI 1 Pin 1 A1B Univ AI 1 Pin 2 A1C Univ AI 1 Pin 3 NC No Connect A2A Univ AI 2 Pin 1 A2B Univ AI 2 Pin 2 A2C Univ AI 2 Pin 3 NC No Connect 12 24VDC I1 I2 I3 I4 I5 I6 I7 I8 H1 H2 H3 H4 0V A1A A1B A1C N C A2A A2B A2C N C 20mA Transmitter T C J3 Orange Green Name Univ AI NC No Connection A3A Univ AI 3 Pin 1 A3B Univ AI 3 Pin 2 A3C Univ AI 3...

Page 4: ...Replace immediately if defective 11 Use copper conductors in Field Wiring only 60 75 C 12 Do not disconnect while circuit is live unless area is known to be non hazardous 13 Do not remove or replace jumpers or connectors while circuit is live unless the area is known to be free of ignitable concentrations of flammable gases or vapors 14 Use caution when making connections to the controller to prot...