Function and structure
Batteries_Rail_Power_Manual_en02.docx
19
5.4.
Technical data
5.4.1.
Overview rail.power blocks/cells
The following table shows an overview of the available rail.power blocks/cells:
Designation
Type
Voltage
[V]
Capacity
[Ah]
Length
[mm]
Width
[mm]
Height
[mm]
Weigth
[kg]
Housing
material
rail.power 12 V 58 Ah
VRLA
12
58
267
177
190
23.0
PP
rail.power 12 V 78 Ah
VRLA
12
78
342
177
190
31.0
PP
rail.power 12 V 115 Ah
VRLA
12
115
344
170
275
46.0
PP
rail.power 12 V 100 Ah
VRLA
12
100
541
125
217
38.5
ABS
*)
rail.power 12 V 130 Ah
VRLA
12
130
541
125
302
58.4
ABS
*)
rail.power 12 V 150 Ah
VRLA
12
150
541
125
302
59.7
ABS
*)
rail.power 12 V 170 Ah
VRLA
12
170
541
125
302
61.1
ABS
*)
rail.power 6 V 170 Ah
VRLA
6
170
242
170
275
32.0
PP
rail.power 6 V 220 Ah
VRLA
6
220
308
170
275
41.0
PP
rail.power 2 V 220 Ah
VRLA
2
220
183
90
310
14.4
ABS
*)
rail.power 2 V 308 Ah
VRLA
2
308
183
129
310
21.7
ABS
*)
rail.power 2 V 375 Ah
VRLA
2
375
183
155
310
25.0
ABS
*)
*) Block/cell also in ABS-FR (Flame Retardent) available, fulfilling the UL94-V0 standard
5.4.2.
Technical details
Construction / Design
•
Cells according to EN 60896 - 21/22
•
VRLA-Battery with electrolyte fixed in a glass fibre fleece
(Absorbent Glass Mat AGM)
•
Battery meets the requirements of EN61373 (shock and
vibration)
Battery designation
rail.power <nominal Voltage> V <nominal Capacity> Ah
Nominal Temperature
20°C
Nominal Capacity
C
5
at 20°C
available capacity for discharge with I
5
(see nameplate) down to
1.6 V per cell at nominal temperature
Nominal Current
I
5
= C
5
/ 5 h (see name plate)
Nominal Voltage Cell
2.0 V / cell
Nominal Voltage Block
6.0 V or 12.0 V
Self Discharge
Ca. 2 to 3% per month at 20 °C
Electrolyte
Diluted sulphuric acid bound in fleece
Valve
Opening pressure 120 mBar
integrated degassing