XNX Universal Transmitter
Installation and Operation
87
Level 1 and Level 2 Passcodes
Level 1 and 2 passcode screens give the administrator the ability
to assign new passcodes for either or both access levels.
From the Configure Security Screen, use the
switches to
highlight Passcode 1. Use
✓
to choose the first digit and the
switches to decrease or increase the values. Use
✓
to accept the
new value and move to the next digit. Repeat until all four digits
have been selected. Follow the same procedure to change the
Level 2 passcode.
Figure 143. Setting the Level 1 passcode
Use the
switches to move to “Accept Settings” on the display.
Choose
✓
to save the settings to the transmitter.
Figure 144. Accept Settings and Security Settings Accepted screens
Verifying the Configuration
Test Menu
The test menu icons are shown in this table:
Symbol
Description
Symbol
Description
X
Inhibit
Force Relay
Force mA Output
Alarm/Fault Simulation
Warning:
Keep the passwords in a secure area to prevent unauthorized access to the
transmitter. If the passwords are lost, resetting the transmitter will require a service
technician.
WARNING
!
X
Inhibit
Warning:
When the transmitter is placed in Inhibit Mode, alarms are silenced. This
will prevent an actual gas event from being reported. Inhibit Mode must be limited to
testing and maintenance only. Exit Inhibit Mode after testing or maintenance activities.
WARNING
!
Figure 145. Inhibit screen
The Inhibit mode is designed to prevent alarms from being
triggered during testing or maintenance.
Summary of Contents for XNX-AM Series
Page 2: ...This page is intentionally left blank ...
Page 7: ...XNX Universal Transmitter Safety and Information 5 Safety and Information ...
Page 12: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 10 Introduction ...
Page 27: ...XNX Universal Transmitter Introduction 25 Menu Navigation ...
Page 102: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 100 Calibration ...
Page 118: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 116 Maintenance ...
Page 122: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 120 Warnings and Faults ...
Page 139: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 137 Specifications ...
Page 174: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 172 Control Drawings ...
Page 177: ...XNX Universal Transmitter Control Drawings 175 ...
Page 179: ...XNX Universal Transmitter Control Drawings 177 Remote Sensor Mount ...
Page 180: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 178 HART Protocol ...
Page 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Modbus Protocol ...
Page 200: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 198 Warranty ...
Page 202: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 200 Index ...