XNX Universal Transmitter
Installation and Operation
74
Range and Alarms
Warning:
XNX Universal Transmitters carrying UL/CSA approvals that are configured
for devices measuring %LEL will not allow adjustments to the full scale value. The
range is fixed at 100%.
WARNING
!
The Range & Alarms option applies only to units with
certifications other than UL/CSA.
Figure 82. Range & Alarms menu
Set Range (full-scale)
Range is sensor dependent. The Set Range option allows the
full-scale range to be set for the sensor which is attached to the
transmitter. The full-scale range is based on the capability of the
sensor. The selectable range for EC sensors is defined in the
Selectable Range column of the table in
.
The selectable range for catalytic bead sensors is defined in the
Selectable Range column of the table in
.
Figure 83. Range Option screen
When the Range option is highlighted, use the switches to
decrease or increase
the value. Use
✓
to accept the displayed
value and move to the next field. When all fields have been
updated, use the switch to highlight
ü
on the right side of the
display. Use
✓
to accept the changes.
✓
Figure 84. Setting the range value
When complete, the display will return to the Range Option
screen.
Set Alarm Values
Set Alarm Values allows the values for Alarm Direction and Alarm
Limits for both Alarm 1 and Alarm 2 to be set.
Caution:
Alarm 1 and Alarm 2 values must be less than the upper limit value.
CAUTION
!
Use Alarm Direction to establish whether the alarm is to be
triggered by rising or falling gas concentrations. Alarms for most
target gases are triggered by rising concentration levels but
certain gases; e.g., oxygen, can be measured for depletion
levels. When the transmitter is configured with mV or OPTIMA
sensors and the meaurement units are LEL, the alarm level
setting is limited to 60%LEL.
If the concentration of the target gas remains above the alarm
values for 3 seconds or more, an alarm will be triggered.
Summary of Contents for XNX-AM Series
Page 2: ...This page is intentionally left blank ...
Page 7: ...XNX Universal Transmitter Safety and Information 5 Safety and Information ...
Page 12: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 10 Introduction ...
Page 27: ...XNX Universal Transmitter Introduction 25 Menu Navigation ...
Page 102: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 100 Calibration ...
Page 118: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 116 Maintenance ...
Page 122: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 120 Warnings and Faults ...
Page 139: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 137 Specifications ...
Page 174: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 172 Control Drawings ...
Page 177: ...XNX Universal Transmitter Control Drawings 175 ...
Page 179: ...XNX Universal Transmitter Control Drawings 177 Remote Sensor Mount ...
Page 180: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 178 HART Protocol ...
Page 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Modbus Protocol ...
Page 200: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 198 Warranty ...
Page 202: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 200 Index ...