XNX Universal Transmitter
Warnings/Faults
121
Warning Messages
Warning
Description
Applicable
Sensors
Latching / Non-Latching
Frequency of Diag-
nostic
Event History Data
Action For Resolution
W001
XNX
®
24 VDC
Supply Bad
All
Non-latching
2 seconds
XNX supply
voltage x1000
Check wire of 24V power supply to XNX as well as power supply opera-
tion.
W002
XNX Tempera-
ture Error
All
Non-latching
2 seconds
XNX tempera-
ture (Celsius)
Check location for heat sources. Fit with sunshade or other protection.
Change location of XNX. Check temperature in Info->Transmitter Status
to ensure temperature is being measured properly.
W003
Simulated
Warning/Fault
All
Non-latching
Enabled by user
0
Performing an alarm/fault reset will clear all simulation.
W005
Sensor Tem-
perature Error
Optima
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or
warning code
(Note 4)
Check location for heat sources. Fit with sunshade or other protection.
Change location of XNX. Check temperature in Info->Sensor Status to
ensure temperature is being measured properly.
Sensor Tem-
perature Error
Excel
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or
warning code
(Note 4)
Check location for heat sources. Fit with sunshade or other protection.
Change location of XNX. Check temperature in Info->Sensor Status to
ensure temperature is being measured properly.
Sensor Tem-
perature Error
ECC
Non-latching
2 seconds
Sensor temper-
ature (Celsius)
Check location for heat sources. Fit with sunshade or other protection.
Change location of XNX. Check temperature in Info->Sensor Status to
ensure temperature is being measured properly.
W006
Negative Drift
ECC, mV
Non-latching
2 seconds
Raw gas con-
centration of
sensor
Check sensor location for external interference. Perform zero calibra-
tion. If problem persists after zero calibration and no interference exists,
replace sensor.
Negative Drift
Optima,
Excel
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or
warning code
Check sensor location for external interference. Perform zero calibra-
tion. If problem persists after zero calibration and no interference exists,
replace sensor.
W007
Calibration
Required
All
Non-latching
2 seconds
Number of days
remaining until
calibration ex-
pires, negative
= number of
days expired
Time since the last span calibration has exceeded a defined limit. Per
-
forming a successful span calibration will clear the condition. The limit is
the user-defined calibration interval. W007 can be disabled by setting the
calibration interval to 0.
Summary of Contents for XNX-AM Series
Page 2: ...This page is intentionally left blank ...
Page 7: ...XNX Universal Transmitter Safety and Information 5 Safety and Information ...
Page 12: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 10 Introduction ...
Page 27: ...XNX Universal Transmitter Introduction 25 Menu Navigation ...
Page 102: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 100 Calibration ...
Page 118: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 116 Maintenance ...
Page 122: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 120 Warnings and Faults ...
Page 139: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 137 Specifications ...
Page 174: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 172 Control Drawings ...
Page 177: ...XNX Universal Transmitter Control Drawings 175 ...
Page 179: ...XNX Universal Transmitter Control Drawings 177 Remote Sensor Mount ...
Page 180: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 178 HART Protocol ...
Page 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Modbus Protocol ...
Page 200: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 198 Warranty ...
Page 202: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 200 Index ...