60
XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005
Applications
NFPA 72-1999 Central or Remote Station Fire Alarm System (Protected Premises Unit)
4.2 NFPA 72-1999 Central or Remote Station Fire Alarm
System (Protected Premises Unit)
Figure 4.1 shows typical wiring diagram for a NFPA 72-1999 Central Station Fire Alarm System
(Protected Premises Unit) or a Remote Station Fire Alarm System (Protected Premises Unit) using
the Universal Digital Alarm Communicator/Transmitter (UDACT) and control panel. This
provides typical wiring only; connect and program the UDACT according to the directions given in
the
UDACT Instruction Manual
.
NOTE:
An NFPA 72-1999 Central Station requires 24 hours of standby power; an
NFPA 72-1999 Remote Station requires 60 hours of standby power.
NOTE:
This application can also be done with the TM-4 Transmitter; refer to the Transmitter
Module TM-4 document for more details.
TB1
3
EIA-485
+ ACS –
24V NONRST 24V RESET
+ – +
–
TB7
UDACT in ABS-8R
(shown with cover removed)
Solid earth
ground
To supervised
phone lines
Ferrite cores
P/N 29090
FACP Cabinet
EIA-485
(ACS Mode)
24 VDC
Nonresettable power
Supervised and power-limited
EIA-485 and power wiring
nfs6
40
-u
da
ct.cd
r
Figure 4.1 Typical Wiring Diagram for a Central Station Fire Alarm System
NOTE:
Install a UL-listed 120 ohm End-of-Line resistor (P/N 71244) UDACT TB1 terminals 3
and 4 if this is the last or only device on EIA-485 line.
Summary of Contents for XLS140
Page 8: ...8 XLS140 Installation Manual Form Number 95 7673 3 P N 51927 C 12 06 2005 ...
Page 57: ...XLS140 Installation Manual Form Number 95 7673 3 P N 51927 C 12 06 2005 57 Notes ...
Page 68: ...68 XLS140 Installation Manual Form Number 95 7673 3 P N 51927 C 12 06 2005 Notes ...
Page 87: ...XLS140 Installation Manual Form Number 95 7673 3 P N 51927 C 12 06 2005 87 ...