Honeywell WSK-HEAT-ROR Installation And Maintenance Instructions Download Page 1

This sensor must be installed in compliance with the control panel system 
installation manual and the SWIFT Wireless Manual. The installation must 
meet the requirements of the Authority Having Jurisdiction (AHJ). Sensors 
offer maximum performance when installed in compliance with the National 
Fire Protection Association (NFPA); see NFPA 72. 

GENERAL DESCRIPTION

Models WSK-HEAT and WSK-HEAT-ROR are intelligent sensors that utilize a 
state-of-the-art thermistor sensing circuit for fast response. These sensors are 
designed to provide open area protection with 50 foot spacing capability as 
approved by UL 521. Model WSK-HEAT is a fixed temperature sensor with 
135°F fixed temperature alarm. Model WSK-HEAT-ROR is a rate-of-rise tem-
perature sensor with 135° F fixed temperature alarm. Rotary dial switches are 
provided for setting the sensor’s address. (Figure 1). Two LEDs on the sensor 
are controlled by the panel to indicate sensor status.

Silent Knight panels offer different features sets across different models. As a 
result, certain features of the WSK-HEAT and WSK-HEAT-ROR may be avail-
able on some control panels, but not on others. The possible features available 
in the WSK-HEAT and WSK-HEAT-ROR, if supported by the control panel are:

•   The panel controls the LED operation on the sensor. Operational modes 

include red, green and amber colors in various solid or blink patterns.

Please refer to the operation manual for the UL listed control panel for specific 
operation of the WSK-HEAT and WSK-HEAT-ROR .

The WSK-HEAT and WSK-HEAT-ROR require compatible addressable com-
munications to function properly. Connect these sensors to listed-compatible 
control panels only.

SPACING

Wireless technologies can exhibit communication disruption if devices are 
spaced too close together. To avoid this form of disruption, SWIFT devices 
should not be placed closer than 2 feet (60 cm) apart without an intervening 
structure.

NOTE: Do not attach the base and detectors to temporary structures such as 
removable ceiling tiles such that the placement could be altered. To prevent 
changes in device placement, permanently secure the structure or mount the 
detector across the ceiling panel support as shown in Figure 2.

I56-427

0-000

INSTALLATION AND MAINTENANCE INSTRUCTIONS

SPECIFICATIONS

Maximum Operating Voltage: 

3.3 VDC

Maximum Standby Current: 

210µA

LED Current: 

10 mA

Maximum Transmit RF Power: 

17dBm

Radio Frequency Range: 

902-928 MHz

Operating Humidity Range: 

10% to 93% Relative Humidity, Non-condensing

Installation Temperature: 

32°F to 100°F (0°C to 38°C)

Fixed Temperature Rating: 

135°F (57°C ) WSK-HEAT and WSK-HEAT-ROR

Rate-of-Rise Detection: 

Responds to greater than 15°F/minute WSK-HEAT-ROR

Battery Type: 

4 Panasonic CR123A or 4 Duracell DL123A

Battery Life: 

2 year minimum

Battery Replacement: 

Upon TROUBLE BATTERY LOW display and/or during annual maintenance

Height: 

2.4˝ (61 mm) installed in B501W Base

Diameter: 

4.0˝ (102 mm) installed in B501W Base

Weight: 

8.1 oz. (230 g) installed in B501W base with 4 batteries

BATTERY REPLACEMENT

Low battery levels on the wireless devices are displayed as a trouble on an 
annunciator. Therefore when the message “TROUBLE BATTERY LOW” is dis-
played, replace the battery in the device. This message is an indication that 
approximately one week of battery life remains.

To replace the batteries in a wireless device use the following steps:

1.  Have 4 CR123A (or DL123A) batteries available
2.  Remove the detector from the base.
3.   Open the battery compartment refer to Figure 3. Note: The battery compart-

ment cover may be left attached at the hinges during battery replacement.

4.   Remove the used batteries and replace with new batteries. The battery 

compartment is designed such that the batteries can only align in the ap-
propriate direction. Do not force the batteries into the openings.

5.  Replace the battery compartment cover.
6.  Return the device to its original location.

CAUTION

Dust covers provide limited protection against airborne dust particles during 
shipping. Dust covers must be removed before the sensors can sense smoke. 
Remove sensors prior to heavy remodeling or construction.

TAMPER RESISTANCE

Models WSK-HEAT and WSK-HEAT-ROR include a tamper-resistant capability 
that prevents their removal from the base without the use of a tool. Refer to 
the base manual for details on making use of this capability. The base also 
includes a magnet for tamper resistance. The magnet activates a supervisory 
tamper fault at the panel if the detector is removed from the base.

TESTING

Before testing, notify the proper authorities that the system is undergoing 
maintenance, and will temporarily be out of service. Disable the system to 

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

C0162-00

FIGURE 1. ROTARY ADDRESS SWITCHES:

12 Clintonville Road, Northford, CT 06472-1610

Phone: 203-484-7161 Fax: 203-484-7118

www.silentknight.com

WSK-HEAT & WSK-HEAT-ROR  

Wireless Intelligent  

Temperature Sensors

  

I56-4270-000 

 

 03-02

Summary of Contents for WSK-HEAT-ROR

Page 1: ...it RF Power 17dBm Radio Frequency Range 902 928 MHz Operating Humidity Range 10 to 93 Relative Humidity Non condensing Installation Temperature 32 F to 100 F 0 C to 38 C Fixed Temperature Rating 135 F 57 C WSK HEAT and WSK HEAT ROR Rate of Rise Detection Responds to greater than 15 F minute WSK HEAT ROR Battery Type 4 Panasonic CR123A or 4 Duracell DL123A Battery Life 2 year minimum Battery Replac...

Page 2: ...est area as shown in Figure 4 to activate the test feature 2 The LEDs should latch on within 10 seconds indicating alarm and an nunciating the panel 3 Reset the detector at the system control panel B Direct Heat Method Hair dryer of 1000 1500 watts 1 From the side of the detector direct the heat toward the sensor Hold the heat source about 6 inches 15 cm away to prevent damage to the cover during ...

Page 3: ...R C2014 01 LED TEST MAGNET MARKER LED TEST MAGNET MARKER FIGURE 5 DETECTOR COMPONENTS FIGURE 4 MAGNET TEST MARKERS C0152 00 FM CLASSIFICATION RTI ratings are for installations which must comply with FM 3210 WSK HEAT RTI FAST WSK HEAT ROR RTI V2 FAST 3 I56 4270 000 03 02 ...

Page 4: ...nufacturer could void the user s authority to operate the equipment FCC STATEMENT Use of these products in combination with non Honeywell products in a wireless mesh network or to access monitor or control devices in a wireless mesh nework via the inter net or another external wide area network may require a separate license from Sipco LLC For more information contact Sipco LLC or Ipco LLC at 8215...

Reviews: