PREFIX 9

Some installations may require a 9 prefix be dialed in order to 

gain a dial tone. The W8735G supports this feature by way of 

the preset jumper. See Fig. 15. When this jumper is in place, a 

“9” will be added to the programmed dial-out number. 

Removing the jumper removes the 9 from the dial-out 

sequence.

Fig. 15. Prefix 9 Jumper.

MULTIPLE DIAL-OUT ATTEMPTS:

The normal communication procedure is for the gateway to 

first attempt a network connection. If this is unavailable, the 

gateway will attempt to dial out via the modem. Multiple 

numbers may be programmed into the gateway as backups 

(check Web App features). Thirty minute periods are allotted 

to each programmed dial-out number, with dial-out attempts 

occurring at approximately five minute intervals. At the end of 

a 30 minute period, the next access number in the queue is 

attempted. This routine is repeated between midnight and 

4:00 

AM

 local time at which point dial-out attempts cease. The 

routine is repeated during the next reporting time of midnight-

4:00 

AM

.

IMPORTANT

For best gateway performance, connect to both the 

network and phone.

Gateway Updates

Periodically, the gateway may require a firmware upgrade to 

enable new features supported by the web application. This 

will occur automatically on a schedule determined by the web 

application administrators.

Battery Replacement

IMPORTANT

For best performance replace the 9V battery yearly 

or as indicated by the LED (as described in Table 2).

The battery backup will ensure that if the power to the 

gateway is out for a period exceeding one hour, the gateway 

will attempt to access the server to announce the outage.

Battery health is monitored constantly. Once a battery is 

replaced, the LED may take a few seconds to reflect the new 

battery.

Battery Installation

1.

Press the latch on the top of the battery cover and pull it 

away from the gateway. See Fig. 16.

2.

Connect 9 Vdc battery to the connector leads.

3.

Insert the battery in the battery compartment.

4.

Insert the bottom tabs of the battery cover into the slots 

on the case, then swing the battery cover until the latch 

engages.

Fig. 16. Battery Installation.

M29955

PREFIX 9 

JUMPER

BATTERY COVER

BATTERY INSTALLED

9V BATTERY LEADS

BATTERY 

COVER LATCH

M23760

Summary of Contents for W8735G

Page 1: ...duct 2 Installer must be a trained experienced service techni cian 3 Complete all wiring connections to the gateway before powering up the 24Vac system transformer and plug ging in the gateway power supply into an outlet 4 All wiring must comply with applicable local electrical codes ordinances and regulations INSTALLATION Mount the W8735G in the equipment room near the indoor HVAC equipment Posit...

Page 2: ...allasts and large distribution pan els Failure to follow these wiring practices may intro duce electrical interference noise which can cause erratic system operation All unused wire is to be grounded at controller end only The bus wire to ter minal 1 D must not exceed 1 000 feet 305 M General Wiring Directions Refer to Fig 3 and Table 1 for the location and function of each terminal IMPORTANT Wire...

Page 3: ...ary Output DO Connect to N O contact alarm input Auxiliary Output DO Connect to N O contact alarm input Auxiliary Input DI Connect to N C sensor contact 18 30 Vac Vdc Auxiliary Input DI Connect to N C sensor contact 18 30 Vac Vdc Channel 3 Model 1018 only 1 D channel 3 To EnviraCOM channel 3 network DATA 2 R channel 3 To EnviraCOM channel 3 network 24 Vac Hot 3 B channel 3 To EnviraCOM channel 3 n...

Page 4: ...MMUNICATION GATEWAY TO OPTIONAL ENVIRACOM CONTROLS AND SENSORS M29961 1 D 2 R 3 B THERMOSTAT OPTIONAL REVIEW COMPONENTS AND ACCESSORIES SECTION FOR COMPATIBLE DEVICES 1 VISIONPRO IAQ 2 2 1 TELEPHONE POWER NETWORK 1 2 3 R7184U OIL PRIMARY CONTROL Status Event Priority Description LED Color Flashes Battery good LOWEST Normal Operation Green Solid Battery low Replace the battery Green Off Battery dea...

Page 5: ...se NOTE The Auxiliary Output is made on all alert conditions and is deactivated when the alert is cleared from the communication bus IMPORTANT Make sure the current draw through the Auxiliary Output terminals does not exceed specifications Use relays or contactors to integrate to line voltage devices Fig 6 AUX IN and AUX OUT Terminals located on the main circuit board Auxiliary Input and Output Ap...

Page 6: ...HANNEL 2 OUTPUT INPUT AUXILIARY POWER FROM THE AUXILIARY INPUT SUPPLIED BY TRANSFORMER 1 T87 OR SIMILAR 1 M23753 1 D 2 R 3 B 1 D 2 R 3 B COMBINATION OF DEVICES CONNECTED IN SERIES TO ANNUNCIATE ON ANY EVENT ON THE AUX IN LOOP 1 CHANNEL 1 CHANNEL 2 OUTPUT INPUT AUXILIARY 1 M23754 1 D 2 R 3 B 1 D 2 R 3 B N C N C COMBINATION OF DEVICES CONNECTED IN PARALLEL TO ANNUNCIATE ON AN AND EVENT ON THE AUX IN...

Page 7: ...ate the server every 30 minutes Applications requiring closer monitoring and faster updates should be connected to a network connection Upon power up the gateway will conduct a self test which includes a broadband or dial up attempt using a pre programmed 800 number Dial up connections are only used in cases where Broadband connections are unavailable For best performance connect to both Network a...

Page 8: ...his routine is repeated between midnight and 4 00 AM local time at which point dial out attempts cease The routine is repeated during the next reporting time of midnight 4 00 AM IMPORTANT For best gateway performance connect to both the network and phone Gateway Updates Periodically the gateway may require a firmware upgrade to enable new features supported by the web application This will occur a...