background image

J. H.  •  7-92  •  © Honeywell Inc. 1992  •  Form Number 69-0726

VVT, VVT-HC (T641A,C)

Floating Control Thermostats

Installation Instructions for the Trained Service Technician.

Application

The VVT and VVT-HC Thermostats provide spdt outputs

to control floating actuators in applications such as variable
air volume (VAV) terminal units.

—VVT (T641A): standard spdt floating control

thermostat.

—VVT-HC (T641C): provides manual heat/cool

changeover switch.

Operation

FLOATING CONTROL

The control provided by the thermostat is conventionally

called floating control. During floating control, a variation of
two-position control, the thermostat provides a three output
control, which is Advance motor, Reverse motor, and Hold.

On a change in temperature, the thermostat drives the

actuator to an intermediate position and then opens the circuit
to the actuator. The actuator remains in this position until
there is a temperature change at the thermostat. The actuator
is said to float between the limits of the thermostat to satisfy
various load requirements.

VAV SYSTEMS

VAV systems control the temperature within a space by

varying the volume of supply air. Air is delivered to the space
at a fixed temperature. The volume of supply air is controlled
by the space thermostat modulating the supply air damper.
When full heating and cooling flexibility is required in a zone,
it is handled by perimeter heating, or reheat capability in the
air terminal units. As individual zones shut down, the total air
flow in the system is regulated by a central duct static pressure
controller. The fan system is sized to handle an average peak
load, not the sum of the individual peaks. Because each zone
peaks at a different time of day, extra air is borrowed from the
off-peak zones. This transfer from low-load to high-load
zones occurs only in true VAV systems.

Pressure dependent systems do not incorporate an indi-

vidual zone air flow sensor and depend on a stable system
pressure to maintain flow. These systems require slower
motors such as the seven minute dampers, which are typically
controlled by the VVT (T641A) or VVT-HC (T641C) Ther-
mostats.

HEAT ANTICIPATION/COOL ANTICIPATION

Control of heating or cooling units with a thermostat does

not allow for the temperature to remain exactly at the thermo-
stat set point, but varies within a certain temperature range.
Anticipation is added to the thermostat to reduce
this range.

The anticipator is a small resistive heater in the thermostat

that heats when the system is on or off. The heat produced by
the anticipator raises the internal bimetal temperature slightly
faster than the surrounding room temperature. The thermo-
stat anticipates the need to shut off the heating system sooner
than it would if affected by room temperature only. The VVT
(T641A) or VVT-HC (T641C) have fixed or voltage antici-
pation.

Installation

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to follow

them could cause a hazardous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for your
application.

3. Installer must be a trained experienced service

technician.

4. After installation is complete, check out product op-

eration as provided in these instructions.

CAUTION

1. Disconnect power supply to prevent electrical

shock or equipment damage.

2. To prevent interference with the thermostat link-

age, keep wire length to a minimum and run
wires as close as possible to the subbase.

3. Do not overtighten thermostat captive mounting

screws, because damage to subbase threads can
result.

4. Do not short across coil terminals on relay. This

can burn out the thermostat heat
anticipator.

IMPORTANT: An incorrectly leveled thermostat will cause

the temperature control to deviate from set point. It is
not a calibration problem.

!

Summary of Contents for VVT

Page 1: ... only in true VAV systems Pressure dependent systems do not incorporate an indi vidual zone air flow sensor and depend on a stable system pressure to maintain flow These systems require slower motorssuchasthesevenminutedampers whicharetypically controlled by the VVT T641A or VVT HC T641C Ther mostats HEAT ANTICIPATION COOL ANTICIPATION Controlofheatingorcoolingunitswithathermostatdoes notallowfort...

Page 2: ...ercury switches See Fig 3 2 Run wiring from the actuator if necessary to the location If the wiring is plastered into the wall make a hole next to the cable and loosen the wires so they can be pushed backintothewalllater Threadwiresthroughholeinpacking materialsavedinstep1 Connectthewirestotheterminalson the back of the thermostat See Fig 4 3 Push the excess wire back through the hole and plug any...

Page 3: ...AL SET POINT LEVER FRONT OF THERMOSTAT COVER REMOVED Y C X W R MOUNTING HOLES 4 BACK OF VVT T641A 4 C X 6 5 MOUNTING HOLES 4 BACK OF VVT HC T641C Fig 3 Mounting thermostat using accessory wallplate 80 70 60 50 WARM COOL HONEYWELL PART NO 221618 ACCESSORY WALLPLATE THERMOSTAT BASE MOUNTING SCREWS 4 THERMOSTAT COVER M6111 EXTERNAL SET POINT LEVER M6110 ...

Page 4: ...en If not adjust the set point of the thermostat higher to determine if the wiring is correct If no movement is ob served check for the presence of 24 Vac between terminals ofthemotorduringacallforcooling Withtheproperwiring and 24 Vac present the actuator should operate correctly If 24 Vac is not present on a call for cooling replace the thermostat To check out the damper when controlled by the t...

Reviews: