VR8215S,T TRADELINE DIRECT IGNITION COMBINATION GAS CONTROLS

7

34-00006EF—01

Check Safety Lockout 

(Slow-Opening Controls Only)

1.

With the system power off and the thermostat set to 

call for heat, manually shut off the gas supply.

2.

Energize ignition control and start timing safety 

lockout time. When spark ignition terminates, stop 

timing.

NOTE: When using the VR8215T, the specified 

ignition control safety lockout time must 

exceed 8.5 seconds for the system to func-

tion properly.

3.

After spark cutoff, manually reopen the gas control 

switch. No gas should flow to the main burner.

4.

Reset the system by adjusting the thermostat below 

room temperature, wait 30 seconds, and then move 

the thermostat setting up to call for heat. Normal 

ignition should occur.

Table 7.  Pressure Regulator Specification 

Pressures in inches wc (kPa).

Check Safety Shutdown 

Performance

WARNING

Fire or Explosion Hazard.

Can cause property damage, severe injury 

or death.

Perform the safety shutdown test any time work is 

done on a gas system.

NOTE: Read steps 1 through 7 before starting, and 

compare to the safety shutdown or safety 

lockout tests recommended for the direct 

ignition (DI) module. Where different, use the 

procedure recommended for the ignition 

module.

1.

Turn off gas supply.

2.

Set thermostat or controller above room 

temperature to call for heat.

3.

Watch for ignition spark or for glow at hot surface 

igniter either immediately or following prepurge. 

See Direct Ignition module specifications.

4.

Time the length of spark operation. See the Direct 

Ignition module specifications.

5.

After the module locks out, open the manual gas 

cock and make sure no gas is flowing to the main 

burner. 

6.

Set the thermostat below room temperature and 

wait one minute.

7.

Operate system through one complete cycle to 

make sure all controls operate properly.

MAINTENANCE

WARNING

Fire or Explosion Hazard.

Can cause property damage, severe injury, 

or death.

Do not disassembly the gas control; it contains 

no replaceable components. Attempted 

disassembly, repair, or cleaning can damage 

the control, resulting in gas leakage.

Regular preventive maintenance is important in 

applications in the commercial cooking and agricultural 

and industrial industries that place a heavy load on 

system controls because:

• In many such applications, particularly commercial 

cooking, the equipment operates 100,000 to 200,000 

cycles per year. Such heavy cycling can wear out the 

gas control in one to two years.

• Exposure to water, dirt, chemicals and heat can 

damage the gas control and shut down the control 

system.

The maintenance program should include regular 

checkout of the control as outlined in the Startup and 

Checkout section, and the control system as described in 

the appliance manufacturer literature.

Maintenance frequency must be determined individually 

for each application. Some considerations are:

• Cycling frequency. Appliances that may cycle 20,000 

times annually should be checked monthly.

• Intermittent use. Appliances that are used seasonally 

should be checked before shutdown and again before 

the next use.

• Consequence of unexpected shutdown. Where the 

cost of an unexpected shutdown would be high, the 

system should be checked more often.

• Dusty, wet, or corrosive environments. Since these 

environments can cause the gas control to deteriorate 

more rapidly, the system should be checked more 

often.

The system should be replaced if:

• It does not perform properly on checkout or 

troubleshooting.

• The gas control is likely to have operated for more than 

200,000 cycles.

• The control is wet or looks as if it has been wet.

SERVICE

WARNING

Fire or Explosion Hazard.

Can cause property damage, severe injury 

or death.

Do not disassemble the gas control; it contains no 

replaceable components. Attempted disassembly, 

repair, or cleaning can damage 

the control, resulting in gas leakage.

CAUTION

Equipment Damage Hazard.

Can burn out thermostats or other 

components in the control string.

Never apply a jumper across (or short) the valve 

coil terminals, even temporarily.

Model 

Type

Type of 

Gas

Nominal 

Inlet 

Pressure 

Range

Factory Set 

Nominal 

Outlet 

Pressure

Setting 

Range

Standard, 

Slow

NAT

5.0–7.0

(1.2–1.7)

3.5

(0.9)

3.0–5.0

(0.8–1.3)

LP

12.0–14.0

(3.0–3.5)

10.0

(2.5)

8.0–12.0

(2.0–3.0)

Summary of Contents for VR8215S

Page 1: ...IFICATIONS Body Pattern Straight through see Table 1 for inlet and outlet size Electrical Ratings Voltage and Frequency 24 Vac 50 60 Hz Current Draw 0 5A Field Wiring 2 1 4 in spade quick connect terminals Capacity See Table 1 Conversion Use conversion factors in Table 2 to convert capacities for other gases Regulation Range See Table 7 Natural LP Gas Conversion Kits See Table 4 Approvals CSA Desi...

Page 2: ...et wet during normal cleaning procedures High Humidity or Dripping Water Dripping water can cause the control to fail Never install an appliance where water can drip on the control In addition high ambient humidity can cause the control to corrode and fail If the appliance is in a humid atmosphere make sure air circulation around the control is adequate to prevent condensation Also regularly check...

Page 3: ...r attempted repair may result in fire or explosion 5 Gas will leak if installed backwards CAUTION Equipment Damage Hazard Can burn out thermostat or transformer Applying a jumper across or shorting the valve coil terminals even temporarily can burn out the thermostat or transformer Follow the appliance manufacturers instructions if available otherwise use these instructions as a guide IMPORTANT Th...

Page 4: ...ed standards and practices 1 Use new properly reamed pipe that is free from chips If tubing is used make sure the ends are square deburred and clean All tubing bends must be smooth and without deformation 2 Run pipe or tubing to the control If tubing is used obtain a tube to pipe coupling to connect the tubing to the control 3 Install a sediment trap in the supply line to the control See Fig 3 Ins...

Page 5: ... volt control in S89 Direct Ignition System STARTUP AND CHECKOUT On Off Switch The on off switch settings are as follows OFF Prevents main gas flow through the control M27669 M27670A ON OFF PRESSURE REGULATOR ADJUSTMENT UNDER CAP SCREW INLET INLET PRESSURE TAP 1 8 IN NPT OUTLET ON OFF SWITCH OUTLET PRESSURE TAP 1 8 IN NPT 24V 24V GND S87B CONTROL MODULE ALARM VALVE VALVE GND TEMPERATURE CONTROLLER...

Page 6: ...eing checked Other appliances must remain off with the pilots extinguished or deduct their consumption from the meter reading Convert flow rate to Btuh as described in form 70 2602 Gas Controls Handbook and compare to Btuh input rating on appliance nameplate 3 IF CHECKING GAS INPUT WITH MANOMETER Make sure the gas control is in the OFF position before removing outlet pressure tap plug to connect m...

Page 7: ...embly repair or cleaning can damage the control resulting in gas leakage Regular preventive maintenance is important in applications in the commercial cooking and agricultural and industrial industries that place a heavy load on system controls because In many such applications particularly commercial cooking the equipment operates 100 000 to 200 000 cycles per year Such heavy cycling can wear out...

Page 8: ...e heating appliance manufacturer The information below describes a typical control application but the specific controls used and the procedures outlined in your appliance manufacturer instructions can differ requiring special instructions To Turn ON Appliance STOP Read the Warnings Above Before Proceeding 1 The lighting sequence on this appliance is automatic do not attempt to manually light the ...

Page 9: ...VR8215S T TRADELINE DIRECT IGNITION COMBINATION GAS CONTROLS 9 34 00006EF 01 ...

Page 10: ...AS CONTROLS Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2014 Honeywell International Inc 34 00006EF 01 M S 11 14 Printed in United States ...

Page 11: ...éro de modèle CARACTÉRISTIQUES Configuration du corps Passage direct voir le Tableau 1 pour la taille d entrée et de sortie Caractéristiques électriques Tension et fréquence 24 V c a 50 60 Hz Appel de courant 0 5 A Câblage sur site Bornes rapides à cosse de po 6 mm Capacité Voir le Tableau 1 Conversion Utiliser les facteurs de conversion du Tableau 2 pour convertir les capacités pour d autres gaz ...

Page 12: ...les n ont lieu que trois ou quatre fois par heure durant la saison de chauffage Pour les applications sur l année entière avec des cadences plus importantes le régulateur peut s user plus rapidement Effectuer une vérification mensuelle Nettoyage à l eau ou à la vapeur Si le régulateur se mouille le remplacer Si l appareil est susceptible d être lavé à l eau ou à la vapeur protéger couvrir le régul...

Page 13: ...ou d explosion Peut causer des dégâts et des blessures graves voire mortelles Respecter ces avertissements avec précision 1 Débrancher l alimentation avant le câblage pour éviter les chocs électriques et les dégâts de l équipement 2 Pour éviter une accumulation dangereuse de gaz combustible couper l alimentation au niveau de la vanne de service de l appareil avant de commencer l installation et ef...

Page 14: ...uivre ces instructions Placer le régulateur de gaz dans une zone bien ventilée Monter le régulateur suffisamment haut au dessus du bas de l armoire pour éviter l exposition à des déversements ou des éclaboussures d eau Veiller à ce que la température ambiante ne dépasse pas les valeurs de température ambiante nominales pour chaque organe Couvrir le régulateur à gaz si l appareil est nettoyé à l ea...

Page 15: ...s dégâts de l équipement 1 Vérifier la tension électrique du régulateur et s assurer qu elle correspond à l alimentation disponible Installer un transformateur et d autres dispositifs si nécessaire 2 Brancher le circuit du régulateur sur les bornes du régulateur Voir les Fig 6 et 7 3 Régler l anticipateur de chaleur du thermostat à 0 50 A la valeur indiquée sur l opérateur de la vanne Dimension de...

Page 16: ...achées qui pourraient causer un retour de flamme dans le vestibule de l appareil 4 Avec le brûleur principal allumé badigeonner les joints du tuyau y compris les douilles et l entrée et la sortie du régulateur avec une solution savonneuse épaisse 5 Si une autre fuite est détectée éteindre le régulateur à gaz et serrer les joints et les raccords du tuyau 6 Remplacer la pièce si la fuite ne peut pas...

Page 17: ...ction de la pression nominale de l appareil Voir le Tableau 7 pour la pression de sortie nominale réglée en usine et la plage de réglage a Retirer la vis d obturation de réglage du régulateur de pression b Avec un tournevis tourner la vis de réglage interne de pression élevée Fig 5 dans le sens des aiguilles d une montre pour l augmenter ou dans le sens contraire des aiguilles d une montre pour ré...

Page 18: ... dans la documentation du fabricant de l appareil La fréquence de l entretien doit être déterminée pour chaque application sur une basse individuelle Voici quelques considérations à prendre en compte Fréquence des cycles Les appareils dont les cycles peuvent avoir lieu 20 000 fois par an doivent être vérifiés mensuellement Utilisation intermittente Les appareils utilisés de manière saisonnière doi...

Page 19: ...uvent différer nécessitant des instructions spéciales Pour mettre l appareil en marche ARRÊTER Lire les avertissements avant de continuer 1 La séquence d allumage de cet appareil est automatique ne pas tenter d allumer le brûleur prin cipal manuellement 2 Si l appareil de chauffage ne s allume pas lorsque le thermostat est réglé à plusieurs degrés au dessus de la température de la pièce régler le ...

Page 20: ... de régulation et d automatisation Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com Marque de commerce déposée aux États Unis 2014 Honeywell International Inc Tous droits réservés 34 00006EF 01 M S 11 14 Imprimé aux États Unis ...

Reviews: