Honeywell VR8215N Installation Instructions Manual Download Page 5

VR8215S,T SINGLE STAGE VR8215Q,N TWO STAGE DIRECT IGNITION GAS CONTROLS

5

69-2253—07

Fig. 5. Typical wiring connections with 24 volt 

control in S89 Direct Ignition System.

STARTUP AND CHECKOUT

On-Off Switch

The on-off switch settings are as follows:
• OFF: Prevents main gas flow through the control.
• ON: Permits gas to flow into the control body. Under 

control of the thermostat and direct ignition 
module, gas can flow to the main burners.

NOTE:

Controls are shipped with the electronic on-
off switch in the ON position.

Perform Gas Leak Test

WARNING

Fire or Explosion Hazard.
Can cause property damage, severe injury 
or death.

Perform Gas Leak Test every time work is done 
on a gas system.

IMPORTANT

Do not spray soap and water solution on the 
gas control. This can damage the control. Do 
not use an excessive amount of soap and 
water solution to perform the gas leak test. 
Apply only to pipe thread areas.

Gas Leak Test

1.

Paint pipe connections upstream of the gas con-
trol with rich soap and water solution. Bubbles 
indicate a gas leak.

2.

If a leak is detected, tighten the pipe connections.

3.

Light the main burner. Stand clear of the main 
burner while lighting to prevent injury caused 
from hidden leaks that could cause flashback in 
the appliance vestibule. 

4.

With the main burner in operation, paint the pipe 
joints (including bushings) and the control inlet 
and outlet with rich soap and water solution.

5.

If another leak is detected, turn the gas control 
to off, tighten the joints and pipe connections.

6.

Replace the part if a leak cannot be stopped.

Turn On System

Push the on-off switch to the ON position.

Turn On Main Burner

Follow appliance manufacturer instructions or turn 
thermostat up to call for heat.

Check and Adjust Gas Input 
and Burner Ignition

IMPORTANT

1. Do not exceed input rating stamped on 

appliance nameplate, or manufacturer’s 
recommended burner orifice pressure for size 
orifice(s) used. Make certain primary air 
supply to main burner is properly adjusted for 
complete combustion. Follow appliance 
manufacturer instructions.

2. IF CHECKING GAS INPUT BY CLOCKING GAS 

METER: Make certain there is no gas flow 
through the meter other than to the appliance 
being checked. Other appliances must remain 
off with the pilots extinguished (or deduct their 
consumption from the meter reading). Convert 
flow rate to Btuh as described in form 
70-2602, Gas Controls Handbook, and 
compare to Btuh input rating on appliance 
nameplate.

3. IF CHECKING GAS INPUT WITH 

MANOMETER: Make sure the gas control is in 
the OFF position before removing outlet 
pressure tap plug to connect manometer 
(pressure gauge). Also move the gas control 
switch back to the OFF position when 
removing the gauge and replacing the plug. 
Before removing inlet pressure tap plug, shut 
off gas supply at the manual valve in the gas 
piping to the appliance or, for LP, at the tank. 
Also shut off gas supply before disconnecting 
manometer and replacing plug. Repeat Gas 
Leak Test at plug with main burner operating.

NOTE:

Check the inlet pressure before adjusting the 
pressure regulator.

Standard (S, Q) and 
Slow-Opening (T, N) Models 

1.

Carefully check the main burner lightoff. Make 
sure that the main burner lights smoothly and 
that all ports remain lit.

2.

Check the full rate manifold pressure listed on 
the appliance nameplate. Gas control full rate 
outlet pressure should match this rating.

3.

With main burner operating, check the control 
flow rate using the meter clocking method or 
check pressure using a manometer connected to 
the outlet pressure tap on the control. See Fig. 7.

WHITE
BLUE
BLACK
BLUE

HOT 

SURFACE

IGNITER-

SENSOR

VALVE

VALVE (GND)
24V

TH-W

24V (GND)

GND (BURNER)

S89C,G,J/S890C,G,J 

HOT SURFACE 

IGNITION CONTROL

L2

HSI

L1

HSI

LIMIT

CONTROLLER

BURNER 

GROUND

THERMOSTAT

OR CONTROLLER

DUAL VALVE 

COMBINATION

GAS CONTROL

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 

PROTECTION AS REQUIRED.  MAKE SURE L1 AND L2 ARE NOT 

REVERSED; THIS WOULD PREVENT FLAME DETECTION.

ALTERNATE LIMIT CONTROLLER LOCATION.

SEN TERMINAL AND Q354 FLAME SENSOR ON D MODELS ONLY.

M27628

L1

(HOT)

L2

VENT 

DAMPER PLUG

1

2

1

2

3

3

SEN

Q354 FLAME

SENSOR

Summary of Contents for VR8215N

Page 1: ... 6 4 mm SPECIFICATIONS Body Pattern Straight through see Table 1 for inlet and outlet size Electrical Ratings Voltage and Frequency 24 Vac 50 60 Hz Current Draw Single Stage 0 5 A Two Stage 0 9 A Field Wiring Single Stage Two 1 4 in spade quick connect terminals Two Stage Molex and spade quick connect terminals two 1 4 in and one 3 16 in Capacity See Table 1 Conversion Use conversion factors in Ta...

Page 2: ... attack the control eventually causing a failure If chemicals are used for routine cleaning avoid contact with the control Where chemicals are suspended in air as in some industrial or agricultural applications protect the control with an enclosure Dust or Grease Accumulation Heavy accumulations of dust or grease can cause the control to malfunction Where dust or grease can be a problem provide co...

Page 3: ...the ambient temperature ratings for each component Cover gas control if appliance is cleaned with water steam or chemicals or to avoid dust and grease accumulation Avoid locating gas control where exposure to corrosive chemical fumes or dripping water are likely Install Piping to Control All piping must comply with local codes and ordinances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 5...

Page 4: ... ignition coils HI Second stage or high fire 4 For single stage controls VR8215S T adjust thermostat heat anticipator to 0 50A rating stamped on valve label For two stage controls VR8215Q N adjust thermostat heat anticipator to 0 90A rating stamped on valve label Fig 4 Typical wiring connections for 24 volt control in S87 Direct Ignition System GAS CONTROL GAS CONTROL HORIZONTAL DROP PIPED GAS SUP...

Page 5: ... burner is properly adjusted for complete combustion Follow appliance manufacturer instructions 2 IF CHECKING GAS INPUT BY CLOCKING GAS METER Make certain there is no gas flow through the meter other than to the appliance being checked Other appliances must remain off with the pilots extinguished or deduct their consumption from the meter reading Convert flow rate to Btuh as described in form 70 2...

Page 6: ...afety Shutdown Performance WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Perform the safety shutdown test any time work is done on a gas system NOTE Read steps 1 through 7 before starting and compare to the safety shutdown or safety lockout tests recommended for the direct ignition DI module Where different use the procedure recommended for the ignition module 1...

Page 7: ... of an unexpected shutdown would be high the system should be checked more often Dusty wet or corrosive environments Since these environments can cause the gas control to deteriorate more rapidly the system should be checked more often The system should be replaced if It does not perform properly on checkout or troubleshooting The gas control is likely to have operated for more than 200 000 cycles...

Page 8: ...g spring 5 Insert the replacement spring See Fig 6 6 Install the new plastic pressure regulator adjust ment screw 7 Check the regulator setting using a manometer or by clocking the gas meter See Check and Adjust Gas Input and Burner Ignition on page 5 8 Adjust regulator by following the Single Stage Regulator Adjust ment process below 9 Reinstall the regulator cap screw 10 Mount conversion label o...

Page 9: ...ting using a manometer or by clocking the gas meter See Check and Adjust Gas Input and Burner Ignition on page 5 8 Adjust high fire first by adjusting exterior 7 16 Hex After high fire has been set adjust low fire utilizing interior 3 32 allen See Fig 8 and the Two Stage Regulator Adjustment process below 9 Reinstall the plastic regulator cap 10 Mount conversion label on the gas control 11 Install...

Page 10: ...e same measurement method to calibrate the low stage Two stage appliance operating sequences vary Consult the appliance manufacturer instructions for the specific operating sequence and for instructions on how to prevent the control from moving to high stage while calibrating the low pressure regulator setting 6 With the main burner operating on low fire cali brate the low fire regulator setting u...

Page 11: ...requiring special instructions To Turn ON Appliance STOP Read the Warnings Above Before Proceeding 1 The lighting sequence on this appliance is automatic do not attempt to manually light the main burner 2 If the furnace does not come on when the thermostat is set several degrees above room temperature set the thermostat to its lowest setting to reset the safety control 3 Remove the burner access p...

Page 12: ...rth Golden Valley MN 55422 3992 customer honeywell com U S Registered Trademark 2017 Honeywell International Inc 69 2253 07 M S Rev 04 17 Printed in United States WEEE Directive At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre Do not dispose of with normal household waste Do not burn ...

Reviews: