Temperature Sensors
H
u
m
idi
st
at
s
an
d
Th
er
m
o
st
at
s
Controller
s
Sensors
Relay
s
Switch
es
Actuators
Va
lv
e
s
Ac
ces
sor
ie
s
En
gi
ne
eri
ng
Gu
ide
Cr
o
s
s
Refere
nc
e
70-6925
47
LP914 Pneumatic Temperature Sensor
One-pipe, direct-acting temperature sensor used with RP908/
RP920 Controllers to provide proportional control of pneumatic
valve or damper actuators. Rod and tube insertion element for
duct, well, or through-the-wall mounting.
•
Corrosion resistant.
•
Continuous temperature indication available by using receiver gage.
LP914 Typical Piping Duct-Mounted Applications
Application Type:
Temperature Sensor
Dimensions, Approximate:
Body: 2 in. high x 2 1/2 in. wide
(Body: 51 mm high x 64 mm wide)
Action:
Direct Acting
Airflow Usage:
0.019 scfm (540 sccm)
Connections:
Push-on barb for 5/32 in. (4 mm) and 1/4 in. (6 mm) O.D.
tubing
Maximum Operating Temperature:
265 F (129 C)
Maximum Operating Pressure:
25 psi (172 kPa)
Output Pressure Range:
3 psi to 15 psi (21 kPa to 103 kPa)
Supply Pressure:
18 psi (124 kPa)
Accessories:
315046A
Well, 1/2 NPT Copper, 15 1/2 in. (392 mm) long
315046B
Well, 1/2 NPT Copper, 7 1/2 in. (191 mm) long
315904A
Well, 1/2 NPT Stainless Steel, 15 7/16 in., 394 mm
315904B
1/2 in. NPT stainless steel Well, 7 5/16 in. (186 mm) long
311085/0107
Sunshield for LP914A1011
Replacement Parts:
14004664-001
0.36 inch diameter Wool felt filter
315602
Inner Filter
M
7
5
6
2
3
1
4
8
9
VALVE
LP914
RP920
M2784
Product Number
Number
of Pipes
Sensor Element
Element Length
Temperature Sensing Range
Mounting
(in.)
(mm)
(F)
(C)
LP914A1003
1
Rod and tube
15 in.
381 mm
-40 F to +160 F
-40 C to +71 C
Duct mount
LP914A1011
1
Rod and tube
27 in.
686 mm
-40 F to +160 F
-40 C to +71 C
Wall
LP914A1029
1
Rod and tube
15 in.
381 mm
40 F to 240 F
5 C to 115 C
Well
LP914A1045
1
Rod and tube
7 in.
178 mm
-40 F to +160 F
-40 C to +71 C
Duct mount
LP914A1052
1
Rod and tube
7 in.
178 mm
40 F to 240 F
5 C to 115 C
Well
LP914A1060
1
Rod and tube
7 in.
178 mm
-40 F to +160 F
-40 C to +71 C
Well
LP914A1144
1
Rod and tube
15 in.
381 mm
25 F to 125 F
-4 C to +52 C
Duct mount
LP914A1151
1
Rod and tube
15 in.
381 mm
-40 F to +160 F
-40 C to +71 C
Duct mount
LP914A1177
1
Rod and tube
15 in.
381 mm
40 F to 240 F
5 C to 115 C
Well
LP914A1193
1
Rod and tube
6 1/2 in.
165 mm
-40 F to +160 F
-40 C to +71 C
Duct mount
LP914A1201
1
Rod and tube
6 1/2 in.
165 mm
40 F to 240 F
5 C to 115 C
Well
LP914A1235
1
Rod and tube
15 in.
381 mm
25 F to 125 F
-4 C to +52 C
Duct mount
LP914A1268
1
Rod and tube
15 in.
381 mm
40 F to 240 F
5 C to 115 C
Duct or Well mount