![Honeywell VisionPRO 8000 Series Product Data Download Page 63](http://html.mh-extra.com/html/honeywell/visionpro-8000-series/visionpro-8000-series_product-data_2158867063.webp)
VISIONPRO® 8000 SMART THERMOSTAT
63
33-00096—04
• Low Limit Temperature Setting
If the cooling system is used to control humidity
while Dehumidification Away Mode is active, the
thermostat allows the cooling system to lower the
indoor air to the Low Limit Temperature Setting to
reach the Dehumidification Setting at ISU 920.
• Temperature Setting
The temperature maintained while
Dehumidification Away Mode is active and the
desired humidity level is satisfied.
• Dehumidification Setting
The desired humidity level while Dehumidification
Away Mode is active.
Fig. 140.
Control Dehumidification Level
1.
Touch MENU and select Dehumidification.
Fig. 141.
Fig. 142.
2.
Select Auto.
Fig. 143.
3.
Touch
or
to select humidity level.
4.
Touch Done to save your settings. Touch Cancel to
ignore changes.
NOTE:
If your air conditioner is used to control humidity,
the temperature may drop up to 3° F below your
temperature setting until humidity reaches the
desired level.
NOTE:
If humidification and dehumidification are setup
to operate in the same system mode (Heat, Cool,
Off), the thermostat will automatically enforce a
15% deadband between the humidification and
dehumidification settings. The thermostat will
automatically switch between humidification and
dehumidification to maintain the desired humidity
level.
Dehumidification - Commercial
The thermostat reads the indoor humidity level and allows
the user to set a dehumidification setting. The thermostat
controls the humidity level using the cooling system or a
dehumidifier.
If humidification and dehumidification are setup to operate
in the same system mode (Heat, Cool, Off), the thermostat
will automatically enforce a 15% deadband between the
MCR34100
MCR34130
Dehumidification
Equipment Status
MCR34131
Dehumidification
Off
Auto