Function Blocks
Function Block Reference Guide
3/99
48
2.15 CARB Function Block,
continued
Configuration Parameters,
continued
RSP
TAB
It looks like this graphically on the Control Builder. Table 2-12 describes the parameters and the value or
selection.
Table 2-12 RSP Tab Configuration Parameters
Properties Group
Parameter
Index#
Parameter Description
Value or Selection
Remote Setpoint
Source and
Units
Use RSP
Input (EU)
N/A
Use Remote Setpoint in
Engineering Units
Click on radio button to
select.
Use RSP
Input (%)
N/A
Use Remote Setpoint in
Percent
Click on radio button to
select.
Use LSP2
(EU)
N/A
Use Local Setpoint #2 in
Engineering Units
Click on radio button to
select.
Ratio/Bias
No Ratio or
Bias
N/A
No ratio and bias applied
to the function block
Click on radio button to
select.
(RSP Input
Only)
Use Local
Bias
Use Bias value selected
on Tab
Click on radio button to select
Enter value at “
Local Bias
Value
” on tab.
Use Bias
Input
Use Bias value attached
to an input to the block
Click on radio button to
select.
Local Bias
Value (EU
)
40
Local bias value in
engineering units
Enter local bias value.
Ratio
39
Gain value for Ratio PID
-20 to +20