T8011R PROGRAMMABLE HEAT PUMP THERMOSTAT
68-0196–1
6
1.
Enter Installer Setup.
a.
Use
▲
or
▼
keys to
set the temperature
setpoint to 52
°
F
(11
°
C).
b.
Press the
▲
and
▼
keys simultaneously for more
than two seconds to enter installer setup.
c.
When released a
software revision code
is displayed.
d.
Press the
▲
key.
Factory configuration
(FC) is displayed
(A typical example is
shown, but information
displayed varies by
model. This information is for factory use only).
Optional System Checkout
When in steps 1c and 1d, pressing the
▼
key can be used to
turn heat or cool outputs on and off. Change the SYSTEM
switch setting to test heat or cool outputs. During testing , the
5 minute off-timer is bypassed. No action takes place if the
system switch is in the Off position.
CAUTION
Damage to Compressor Possible.
Allow compressor to remain off for 5 minutes
before restarting.
Refer to manufacturer's instructions.
Examples: System setting at HEAT: Press the
▼
key to turn
on the first stage heat. Press the
▼
key again to
turn on the second stage heat. To turn off second
stage heat, press the
▼
key a third time. Press
the
▼
key again to turn off the first stage heat.
System setting at COOL: If cool is on, pressing
the
▼
key turns it off; if cool is off, pressing the
▼
key turns it on.
NOTE:
In Installer Setup only, each press of the
▲
key momentarily displays 1. Each press of the
▼
key momentarily displays 2. When the keys
are released, these one-digit codes are no
longer displayed.
2.
Setting
°
C or
°
F.
a.
Press the
▲
key again
to display the current
setting.
b.
Press the
▼
key to
change the
°
C or
°
F
indication.
3.
Setting Heat Cycle Rate (see Table 1 for cycle rate
options).
NOTE:
Cycle rate settings are for second stage heat.
First stage heat and cool are fixed at 3 cph.
a.
Press the
▲
key to
display the current
heat cycle rate setting
of 1, 3, 6, or 9 cph.
b.
If the desired cycle rate
is displayed, press the
▲
key to exit the installer setup.
c.
To change the heat
cycle rate, press the
▼
key until your choice of
1, 3, 6, or 9 is
displayed.
d.
Press the
▲
key to
display cooling
algorithm configuration
default.
e.
Press the
▲
key again
to change cooling
algorithm to C1 or C3.
C1 = Standard cooling algorithm.
C3 = Agressive cooling algorithm (can cause
overshooting).
f.
Press the
▲
key
again. Current
configuration (CC) is
displayed. A typical
example is shown, but
CC varies by model.
(This information is for factory use only.)
4.
Exit Installer
Setup.
a.
Press the
▲
key to
save all
changes
and return to normal operation.
Table 1. Second Stage Heating Cycle Rates.
OPERATION
Setting FAN and SYSTEM Switches
Fan and system settings are controlled manually by using the
switches located at the bottom of the thermostat case.
See Fig. 8.
System
Cycles Per Hour
Steam, Gravity1
Condensing Gas Furnaces
a
3
Gas or Oil Forced Air
6
Electric Heat
9
a
High efficiency furnace (90+).