INSTALLATION INSTRUCTIONS

62-0271-07

Zio

®

/Zio Plus LCD Wall Modules

TR70, TR71 and TR75 models with Sylk

®

 bus

PRODUCT DESCRIPTION

The TR70, TR71 and TR75 are 2-wire, non-polarity sensitive, 

Sylk bus communicating wall modules, which communicate 

with Spyder

®

 and some ComfortPoint™ programmable 

controllers.

All models have a space-temperature sensor, network bus 

jack, and an LCD panel with three softkeys and two Up/Down 

adjustment keys. The TR70-H, TR71-H and TR75-H models 

include an onboard humidity sensor.

NOTES:

1.

Refer to the 

Zio/Zio Plus LCD Wall Modules  – 

Specification Data

, form 63-1322, for specific 

model features and additional information.

2.

Refer to the 

Zio/Zio Plus LCD Wall Modules – 

Operating Guide

 (Form 63-2719) for information 

about customizing the wall module configuration, 

such as modifying the default Home screens or 

creating your own application.

FEATURES

The 

Zio

 wall modules include:

• Ability to control user access to controller parameters, 

including password protection on TR71 and TR75 

models.

• Ability to assign labels for enumerated values.

• Customized parameter access, by using the WEBs-AX 

Workbench tool.

• Ability to link setpoint limits to a network variable.
• Programmable for: home screen options, tenant 

access, contractor access, access to controller 

parameters, setpoint, override, fan, and other 

parameters.

• TR70 and TR71 have the ability to access and adjust 

virtually any parameter in the programmable controller 

(except Scheduling).

• TR75 can additionally access and adjust the controller 

schedule.

• The TR71 has roughly twice the memory capacity for 

parameters as the TR70, and the TR75 has more than 

twice the memory capacity for parameters as the TR71.

• Ability to balance the VAV system from the wall module.
• Home screen can display one to three of any of the 

following parameters: temperature setpoint, room 

temperature, room humidity, outdoor humidity, 

outdoor temperature, and time, or one of virtually any 

parameter in the controller.

• Network  bus  jack.
• Simple 2-wire terminal connection to the 

programmable controller and an optional 2-wire 

terminal connection for the network. All connections 

are polarity insensitive.

• Permanent retention of user configuration, including 

setpoints after a power outage.

SPECIFICATIONS

Models: 

TR70, TR71, TR75.

TR70-H, TR71-H and TR75-H include an onboard 

humidity sensor.

Environmental Ratings:

• Operating Temperature: 30°F to 110°F (-1°C to 43°C)

• Shipping Temperature: -40°F to 150°F (-40°C to 65.5°C)

• Relative Humidity: 5% to 95% non-condensing

Accessories:

50007298-001 (pack of 12) medium, cover plate; 

6-7/8 x 5 in. (175 x 127 mm).

Approvals:

 CE; UL94-HB plastic enclosure; FCC Part 15, 

Class B

Summary of Contents for TR70

Page 1: ...tions tenant access contractor access access to controller parameters setpoint override fan and other parameters TR70 and TR71 have the ability to access and adjust virtually any parameter in the programmable controller except Scheduling TR75 can additionally access and adjust the controller schedule The TR71 has roughly twice the memory capacity for parameters as the TR70 and the TR75 has more th...

Page 2: ...es or as specified on installation wiring dia grams Wall module wiring can be sized from 18 to 24 AWG 0 82 to 0 20 sq mm depending on the application For multiple Zios on the same S BUS 24 AWG wire is recommended For S BUS wiring the Zio may be mounted up to 200 ft 61 m from the programmable controller If multiple Zios are installed the total distance from the controller to the last Zio should not...

Page 3: ... from the conductor See Fig 5 for wiring multiple Zios 2 Insert the wire in the required terminal location and tighten the screw to complete the termination 3 Review and verify the terminal connection wiring illustrated in Fig 6 NOTE The recommended wire size for the network bus and S BUS is Level IV 22 AWG 0 34 sq mm ple num or non plenum rated unshielded twisted pair solid conductor wire However...

Page 4: ...ng Wall Module from Subbase POWER UP After the wall module is properly wired to the controller it will power up Upon initial power up the wall module LCD panel displays the phrase PLEASE LOAd see Fig 8 This phrase alternates with bus address model and version number TR71 and TR75 only and any onboard sensor display such as temperature humidity etc Refer to the Zio Zio Plus LCD Wall Modules Operati...

Reviews: