Heating-Cooling Thermostats

INSTALLATION  INSTRUCTIONS

Installation Instructions for the Trained Service Technician.

APPLICATION

T841  Thermostats provide 24 Vac control of multistage 

heating and cooling systems  using manual changeover. 

The T841D controls  1-stage heat and 2-stage cool and the 
T841E controls 2-stage gas heat and  1-stage cool. The 
T841D,E,  provide  HEAT-OFF-COOL system switching 
and AUTO-ON fan switching.

Test holes are provided on the front of the thermostat to 
accommodate test meter probes without removing the 
thermostat from the wall.  Remove the cover of the 
thermostat to expose the test holes, which are labeled to 
correspond with terminals on back of the thermostat.  See 

Fig.  1.

Table 1. Thermostat Features.

Order Number

LEDs

Terminal D esignations

System Switch

Fan Switch

Fig.

T841D

CHECK,  HI  SPD,  LO  SPD

R,G,W,B,L,X,Y1,Y2,O

HEAT-OFF-COOL

AUTO-ON

2

T841E

HI,  LOW

R,G,W1,B,W2,Y

HEAT-OFF-COOL

AUTO-ON

3

F R O N T   O F   D E V I C E

B A C K   O F   D E V I C E

-S Y S T E M   SW ITCH

FAN  SW ITCH

THERMO METER

SETPOINT
SCALE

-  LED (UP 

TO THREE)

MOUNTING 
H OLES (4)

W IRIN G  TERM INAL  1

 

(UP TO  12)

COVER

Fig.  1. External view of T841.

OPERATION

The T841E stages of heat 

make

 sequentially as the 

temperature drops. 

Make

 refers to the mercury switch 

initiating a call for heat or cool.

There is about  1 °F (0.6°C) between stages so the second 
stage (auxiliary heat)  makes only when the first stage 
cannot handle the load. This 1°F is the 

interstage d

i

fferen­

tial.

 The T841D stages of COOL-ON  make sequentially as 

the temperature  rises.

The light emitting diodes (LED) indicators light on certain 
thermostats when something specific happens within the 
system.  Refer to the following list when the LED lights:

HI:  Stage two of heat is operating.

LOW:  Stage one of heat is operating.

CHECK:  System needs to be checked.  See heating 

system instructions for specific meaning.

HI  SPD:  Stage two of cooling is operating.

LO SPD:  Stage one of cooling is operating.

LEDs are not field replaceable.

®U.S.  Registered  Trademark

Copyright ©   1997  Honeywell  Inc.

A ll  R ig h ts  R e served

69-1066

Summary of Contents for t841e

Page 1: ...COOL AUTO ON 3 F R O N T O F D E V IC E B A C K O F D E V IC E SYS TEM SWITCH FAN SWITCH THERMOMETER SETPOINT SCALE LED UP TO THREE MOUNTING HOLES 4 WIRING TERMINAL 1 UP TO 12 COVER Fig 1 External view of T841 OPERATION The T841E stages of heat make sequentially as the temperature drops Make refers to the mercury switch initiating a call for heat or cool There is about 1 F 0 6 C between stages so ...

Page 2: ...l behind the thermostat This thermostat is a precision instrument and was carefully adjusted at the factory Handle carefully Mounting and Wiring The T841 can be mounted directly to a wall or horizontal outlet box Choose the method that best fits your installation In replacement applications check the existing thermo stat wires for cracked or frayed insulation Replace any wires in poor condition Al...

Page 3: ...ig 2 Internal schematic and typical wiring diagram for T841D Provides 1 stage heating and 2 stage cooling control Fig 3 Internal schematic and typical wiring diagram for T841E Provides 2 stage heating and 1 stage cooling control 3 69 1066 ...

Page 4: ... switch to AUTO Move the setpoint lever to about 10 F 6 C above room temperature Heating should start The fan should start after a short delay Move the setpoint lever about 10 F 6 C below room temperature Heating should shut off The fan will shut off after a short delay Cooling A CAUTION Do not operate cooling if outdoor temperature is below 50 F 10 C Refer to the manufacturer recommendations Move...

Reviews: