Revision 4.0
STT850 Series HART/DE Option User’s Manual
Page 69
6.8.2 Correct Input at URV
1.
Select the
Correct URV
button. This message appears.
2.
Adjust the PV input Temperature to
the
exact value of the URV
entered
in the DE
CONFIGURE display.
3.
Select the
OK
button.
4.
When the transmitter has completed the URV correction, this message appears.
5.
Select
OK
to acknowledge.