Table 21. Smart VFD HVAC technical data
Ambient conditions
(cont.)
Vibration
EN61800-5-1/
EN60068-2-6
5…150 Hz
Displacement amplitude
1 mm (peak) at
5…15.8 Hz (MR4…MR9)
Max acceleration amplitude
1 G at
15.8…150 Hz (MR4…MR9)
Shock
EN61800-5-1
EN60068-2-27
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in
package)
Enclosure class
IP21/NEMA 1 standard in entire kW/HP range
IP54/NEMA12 option
Note! Keypad required for IP54/NEMA12
EMC (at default
settings)
Immunity
Fulfils EN61800-3 (2004), first and second
environment
Emissions
Depend on EMC level.
+EMC2: EN61800-3 (2004), Category C2
Honeywell Smart VFD HVAC will be deliv-
ered with class C2 EMC filtering, if not oth-
erwise specified.
Honeywell Smart VFD HVAC can be modi-
fied for IT-networks. See chapter 5.2.
Emissions
Average noise level
(cooling fan) sound
power level in dB(A)
MR4: 65
MR7: 77
MR5: 70
MR8: 86
MR6: 77
MR9: 87
Safety
EN 61800-5-1 (2007), CE, cUL; (see unit
nameplate for more detailed approvals)
Control connections
See chapter 7.2.1.
Protections
Overvoltage trip limit
Undervoltage trip limit
Yes
Yes
Ground fault protection In case of ground fault in motor or motor
cable, only the drive is protected
Mains supervision
Yes
Motor phase supervision Trips if any of the output phases is missing
Overcurrent protection Yes
Unit overtemperature
protection
Yes
Protections (cont.)
Motor overload protection Yes
Motor stall protection
Yes
Motor underload
protection
Yes
Short-circuit protection
of +24V and +10V
reference voltages
Yes