3. Installation
3.12. Remote antenna
Revision 2
SmartLine Wireles User's Manual
31
3.12 Remote antenna
Outdoor installation warnings
WARNING
LIVES MAY BE AT RISK! Carefully observe these instructions and any special instructions
that are included with the equipment you are installing.
WARNING
Contacting power lines can be lethal.
Look over the site before beginning any installation, and anticipate possible hazards,
especially these:
Make sure no power lines are anywhere where possible contact can be made. Antennas,
masts, towers, guy wires or cables may lean or fall and contact these lines. People may be
injured or killed if they are touching or holding any part of equipment when it contacts electric
lines. Make sure there is NO possibility that equipment or personnel can come in contact
directly or indirectly with power lines.
Assume all overhead lines are power lines.
The horizontal distance from a tower, mast or antenna to the nearest power line should be at
least twice the total length of the mast/antenna combination. This will ensure that the mast will
not contact power if it falls either during installation or later.
WARNING
To avoid falling, use safe procedures when working at heights above ground.
Select equipment locations that will allow safe, simple equipment installation.
Don’t work alone. A friend or co-worker can save your life if an accident happens.
Use approved non-conducting ladders and other safety equipment. Make sure all equipment is
in good repair.
If a tower or mast begins falling, don’t attempt to catch it. Stand back and let it fall.
If anything such as a wire or mast does come in contact with a power line, DON’T TOUCH IT
OR ATTEMPT TO MOVE IT. Instead, save your life by calling the power company.
Don’t attempt to erect antennas or towers on windy days.
WARNING
MAKE SURE ALL TOWERS AND MASTS ARE SECURELY GROUNDED, AND
ELECTRICAL CABLES CONNECTED TO ANTENNAS HAVE LIGHTNING ARRESTORS.
This will help prevent fire damage or human injury in case of lightning, static build-up, or short
circuit within equipment connected to the antenna.
The base of the antenna mast or tower must be connected directly to the building protective
ground or to one or more approved grounding rods, using 1 OAWG ground wire and
corrosion-resistant connectors.
Refer to the National Electrical Code for grounding details.
Lightning arrestors for antenna feed coaxial cables are available from HyperLink
Technologies, Inc.
Summary of Contents for SmartLine
Page 2: ......
Page 8: ......
Page 14: ...xiv SmartLine Wireless User s Manual Revision 2 ...
Page 109: ...Revision 2 SmartLine Wireless User s Manual 95 ...
Page 110: ...96 SmartLine Wireless User s Manual Revision 2 ...
Page 111: ...Revision 2 SmartLine Wireless User s Manual 97 ...
Page 119: ...Revision 2 SmartLine Wireless User s Manual 105 B5 Control Drawing ...
Page 120: ...106 SmartLine Wireless User s Manual Revision 2 ...
Page 121: ...Revision 2 SmartLine Wireless User s Manual 107 ...
Page 122: ...108 SmartLine Wireless User s Manual Revision 2 ...
Page 123: ...Revision 2 SmartLine Wireless User s Manual 109 ...
Page 128: ...114 SmartLine Wireless User s Manual Revision 2 This page has been intentionally left blank ...