Honeywell
• 49
C
ONTROL
UNIT
5.2
I/O cabling and fieldbus connection
The drive can be connected to fieldbus either through RS485 or Ethernet. The connection for
RS485 is on the standard I/O board (terminals A and B) and the connection for Ethernet is un-
der the drive cover, left to the control keypad. See Figure 44.
Figure 44.
5.2.1
Prepare for use through Ethernet
5.2.1.1
Ethernet cable data
Table 25. Ethernet cable data
Connector
Shielded RJ45 connector;
NOTE:
Max
length of the connector 40mm.
Cable type
CAT5e STP
Cable length
Max .100m
1
Connect the Ethernet cable (see specification on page 49) to its terminal and run
the cable through the conduit as shown in Figure 45.
NOTE:
Pay attention that the length of the connector does not exceed 40 mm.
See Figure 50.
Ethernet
connector
Ethernet
cable run
conduit
I/O terminal
(see larger
picture)
Grounding
bar
DIP
switches
32 33
12 13 14 15 16 17 18 19 30
B
A
RS485 terminals
A = Data- B = Data+
21 22 23
24 25 26
1 2 3 4 5 6 7 8 9 10 11