Honeywell Silent Knight SK-Relay-6 Installation And Maintenance Instructions Download Page 1

SK-460-007 

I56-3439-000

INSTALLATION AND MAINTENANCE INSTRUCTIONS

I56-3439-000

7550 Meridian Circle, Maple Grove, MN 55369-4927

763.493.6455, 800.328.0103; Fax: 763.493.6475

http://www.silentknight.com

SK-Relay-6
Six Relay Control Module

SPECIFICATIONS

Normal Operating Voltage: 

15-32 VDC Stand-By Current:1.45 mA

Alarm Current: 

32 mA (assumes all six relays have been switched once and all six LEDs solid on)

Temperature Range: 

32°F to 120°F (0°C to 49°C)

Humidity: 

10 to 85% Non-condensing

Dimensions: 

6.8˝ H × 5.8˝ W × 1.0˝ D 

Accessories: 

IDP-ACB cabinet and chassis

Wire Gauge: 

12-18 AWG

Relay Current: 

30 mA/Relay Pulse (15.6 mS pulse duration) pulse under panel control

BEFORE INSTALLING

If the modules will be installed in an existing operational system, inform the 
operator and local authority that the system will be temporarily out of service. 
Disconnect the power to the control panel before installing the modules. This 
system contains static sensitive components. Always ground yourself with a 
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably 
grounded.

NOTICE: This manual should be left with the owner/user of this equipment.  

GENERAL DESCRIPTION

The SK-Relay-6 Six Relay Control Module is intended for use in an intelligent 
alarm  system.  Each  module  is  intended  for  Form-C  switching  applications, 
which do not require wiring supervision for the load circuit. A single isolated 
set  of  dry  relay  contacts  is  provided  for  each  module,  which  is  capable  of 
being wired for either normally open or normally closed for each operation. 
Each module has its own address. A pair of rotary code switches is used to set 
the address of the first module from 01 to 94(or 01 to 154 for panels that sup-
port 159 addresses). The remaining modules are automatically assigned to the 
next five higher addresses. Provisions are included for disabling a maximum 
of three unused modules to release the addresses to be used elsewhere. Each 
SK-Relay-6 module also has panel controlled green LED indicators. The panel 
can cause the LEDs to blink, latch on, or latch off.

Contents include:.

(6)  1 × 3 Terminal Blocks 
(1)  1 × 4 Terminal Blocks
(2)  11/4˝ (32mm) Stand offs
(4)  Machine Screws
(2)  Nuts
(1)   Shunt (NOTE:  For the disable position, not more than one shunt shall be 

installed at the same time)

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a compatible 
Silent Knight system control panel. 

CURRENT RATING

MAXIMUM VOLTAGE

LOAD DESCRIPTION

APPLICATION

3 A

30 VDC

Resistive

Non-coded

2 A

30 VDC

Resistive

Coded

.9 A

110 VDC

Resistive

Non-coded

.9 A

125 VDC

Resistive

Non-coded

.5 A

30 VDC

Inductive (L/R=5ms)

Coded

1 A

30 VDC

Inductive (L/R=2ms)

Coded

.3 A

125 VAC

Inductive (PF=.35)

Non-coded

1.5 A

25 VAC

Inductive (PF = .35)

Non-coded

.7 A

70.7 VAC

Inductive (PF=.35)

Non-coded

2 A

25 VAC

Inductive (PF=.35)

Non-coded

WARNING

All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that 
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.