Honeywell SILENT KNIGHT SK-FML Installation Instructions Download Page 1

P/N LS10178-001SK-E Rev A

ECN: 17-0196

 

SK-FML/SK-FSL Fiber Option 
Modules Installation Instructions

Section 2: SK-FML/SK-FSL
                  Specifications

Table 2.1 lists the SK-FML multi-mode fiber-optic 
digital audio ports specifications.

Table 2.2 lists the SK-FSL single-mode fiber-optic 
digital audio ports specifications.

Section 1: Description

The Silent Knight/Farenhyt Emergency 
Communication Systems that use the ECS-NVCM 
(Network Voice Control Module) and the Silent 
Knight/Farenhyt Fire Alarm Control Panels that use 
the SK-NIC (Network Interface Card) support two 
types of fiber-option modules to convert wire to fiber.
• SK-FML (Fiber-Optic 

Multi-Mode, Receiver)

• SK-FSL (Fiber-Optic 

Single-Mode, 

Transmitter)

SK-FML (Fiber-Optic Multi-Mode, Receiver)

The SK-FML is a fiber module that is used as one 
channel to transmit or receive communications with 
the ECS-NVCM (Network Voice Control Module) or 
SK-NIC (Network Interface Card). It allows the multi-
mode fiber to network between the SK-FML module 
boards.
Figure 1.1 illustrates the SK-FML fiber module.

Figure 1.1 SK-FML Circuit Board

SK-FSL (Fiber-Optic Single-Mode, Transmitter)

The SK-FSL is a fiber module that is used as one 
channel to transmit or receive communications with 
the ECS-NVCM (Network Voice Control Module) or 
SK-NIC (Network Interface Card). It allows the 
single-mode fiber to network between the SK-FSL 
module boards.
Figure 1.2 shows the SK-FSL fiber module.

Figure 1.2 SK-FSL Circuit Board

Table 1.1 lists the models that are assigned to the 
ECS-NVCM and SK-NIC. 

ECS-NVCM

SK-NIC

IFP-2100ECS    IFP-75

IFP-2100   6808

IFP-300ECS

IFP-300   6700

6820/6820EVS 

Table 1.1 Network Voice and Interface Card 

Modules

SK-FML Specifications

Type of Connector:

Type ST

Maximum 
Attenuation: 

8 dbB for multi-mode with 
62.5/125 micrometer cable 
@ 200 µ.

Current Draw:

Standby Current:

0.053 A

Alarm Current:

0.053 A

Environment Rating: 32° to 120°F (0° to 49°C), 

0% to 93%   

Relative Humidity:

Non-condensing at 90°F (30°C)

Table 2.1 SK-FML 

SK-FSL Specifications

Type of Connector: Type LC

Maximum 
Attenuation: 

30 dB for multi-mode with 9/125 
micrometer cable @ 1310 nm.

Current Draw:

Standby Current:

0.079 A

Alarm Current:

0.079 A

Environment Rating: 32° to 120°F (0° to 49°C), 

0% to 93%   

Relative Humidity:

Non-condensing at 90°F (30°C)

Table 2.2 SK-FSL 

firealarmresources.com

Summary of Contents for SILENT KNIGHT SK-FML

Page 1: ...e Figure 1 1 SK FML Circuit Board SK FSL Fiber Optic Single Mode Transmitter The SK FSL is a fiber module that is used as one channel to transmit or receive communications with the ECS NVCM Network Voice Control Module or SK NIC Network Interface Card It allows the single mode fiber to network between the SK FSL module boards Figure 1 2 shows the SK FSL fiber module Figure 1 2 SK FSL Circuit Board...

Page 2: ...s static shield bag observing proper static protection measures 2 Visually inspect the unit for damage If any components are damaged notify the shipping carrier immediately Report missing components to the Silent Knight Customer Service 3 Use the Hardware Kit provided with the unit 4 Plug the Fiber Module 1 into P6 of the ECS NVCM or SK NIC circuit as shown in Location 1 in Figure 3 2 1 and Figure...

Page 3: ...tput power for the transmitting fiber See Table 4 2 2 SW1 4 Not used P1 Plugs onto P5 Port 1 or P6 Port 2 of the ECS NVCM or SK NIC NOTE Use standard ST connector fiber optic cable multi mode up to 200 µ optimized for 62 5 125 µ Signal loss up to 8dB maximum between nodes Table 4 2 1 SK FML Terminal Wiring Designations J2 J1 FIBER IN FIBER OUT SW1 1 SW1 2 SW1 3 Drive Current OFF OFF OFF 10 mA OFF ...

Page 4: ... flickers and turns ON If no activity is detected the TX light turns OFF 2 RX Green Lights while data is received on the Repeater When activity is detected the RX light flickers and turns ON When no activity is detected the RX light turns OFF Table 4 4 2 SK FSL LED Indicators Part Number Title LS10143 001SK E IFP 2100 ECS Installation and Operation Manual LS10144 001SK E 6820 EVS Installation and ...

Reviews: