Operation
P/N 151204
5-9
5.7
System Testing
This section describes operation of fire drills, zone testing, and the 24-hour automatic test.
5.7.1
Fire Drills
Fire drills can be run from either the on-board touchpad or the Model SK-5235 Remote
Annunciator. To initiate a fire drill, press
+ Code. The system will sound an
alarm and report a fire test. To end the fire drill, press
+ Code.
5.7.2
Walk Test
The walk test is designed to be used for on-site testing only.
To enter walk test mode, press
+ Installer Code.
Select the following test parameters:
The LCD will indicate that you are in walk test mode. When a zone is tripped, the SK-5208
will activate the bell outputs for approximately six second and will cycle smoke power off and
on for the programmed time interval. When smoke power is restored, there is a two-second
power up delay before the zone will respond to additional test inputs.
The system will time out and resume normal operation in 30 minutes if no keys are pressed or
no zones are tripped during the walk test.
To exit walk test mode, press
.
5.7.3
Automatic Self Test
The Model SK-5208 lets you select the time of day that the 24-hour automatic test signal will
be sent to the central station. See Sections 4.2.10 and 4.3 for additional information on
automatic test time.
5.7.4
Watchdog Circuit
During normal operation, the control microprocessor of the SK-5208 is constantly running
programs to check inputs and carry out other routine functions. If the program should ever
stop running, the watchdog circuit will automatically detect this and attempt to resume normal
operation by resetting the microprocessors. Each time the watchdog circuit initiates a reset
signal, it will also sound the audible trouble signal for approximately four seconds.
Test Feature
Enable or
Disable
Comments
Use Verify:
Yes or No
If Yes is selected then this option will be enabled during
walk test. If No is selected this option will be disabled
during walk test.
Mapped Rlys:
Yes or No
Mapped NACs:
Yes or No
2
0
2
2
firealarmresources.com
Summary of Contents for SILENT KNIGHT SK-5208
Page 2: ...firealarmresources com ...
Page 8: ...Installation Manual iv firealarmresources com ...
Page 9: ...Contents v firealarmresources com ...
Page 10: ...Installation Manual vi firealarmresources com ...
Page 17: ...Agency Listings and Requirements P N 151204 2 3 firealarmresources com ...
Page 118: ...firealarmresources com ...
Page 120: ...Cut Along the Dotted Line firealarmresources com ...
Page 121: ...firealarmresources com ...