
IFP-2000 Installation Manual
5-6
151430
5.4.2
Network Repeater Installation
The network repeater mounts in its own cabinet. The cabinet must be placed within 2 feet of
the main control panel cabinet in order for the 5 foot ribbon cable to reach between the
repeater and the control panel.
Figure 5-5 Network Repeater mounted in cabinet
Use the following steps to properly mount the network repeater to the IFP-2000.
1. Place the network repeater cabinet within 2’ of the IFP-2000 panel. Use 3/4”or larger
conduit between the IFP-2000 and the repeater cabinet. Install the repeater PCB in the
repeater cabinet using the mounting hardware provided.
firealarmresources.com
Summary of Contents for Silent Knight IFP-2000 Module 3
Page 2: ...firealarmresources com ...
Page 12: ...IFP 2000 Installation Manual viii firealarmresources com ...
Page 22: ...IFP 2000 Installation Manual 1 10 151430 firealarmresources com ...
Page 26: ...IFP 2000 Installation Manual 2 4 151430 firealarmresources com ...
Page 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example firealarmresources com ...
Page 100: ...IFP 2000 Installation Manual 5 14 151430 firealarmresources com ...
Page 194: ...IFP 2000 Installation Manual 10 20 151430 firealarmresources com ...
Page 210: ...IFP 2000 Installation Manual 12 8 151430 firealarmresources com ...
Page 230: ...IFP 2000 Installation Manual A 14 firealarmresources com ...
Page 232: ...IFP 2000 Installation Manual B 2 151430 firealarmresources com ...
Page 236: ...firealarmresources com ...
Page 237: ...firealarmresources com ...