GB
Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway
http://www.hls-nordic.com
PE N L
PE N L
washer
rubber
o-ring
PE N L
PE N L
MOUNTING METHODS
Surface mounting on the wall
3
6
2
5
1
4
INSTALLATION
Step 1:
Unfasten the front screw and remove the cover. Next, unfasten the four retaining screws without
removing them and remove the diffusor.
Step 3
: Use a drill with a 3,5mm bit to open the 4 mounting holes located in the plastic base. Place the
luminaire on the desired mounting location and mark and drill these 4 holes. Fit the supplied 4
plastic mounting plugs to these drilled holes on the mounting location.
Step 2
: Install the supplied cable gasket from the inside of the plastic base.
Step 4:
Open a cable entry cutout hole on the plastic base and install the supplied cable gasket. Make a
hole in the center into the desired gasket by using a small screwdriver and pass the round cable
through the gasket. Connect the main cables to the respective terminal block: N for neutral, L for
live wire and PE for ground wire. Install the included tie (if needed) to fasten securely the power
cables. Always use in any case round mains cable, with a diameter of 5-10mm (H05RN-F type
2x1mm² or any other type, at least equal to it's mechanical and electrical properties). ATTENTION!!
The cable must not be deformed in any way (This requirement is important to ensure the IP rating).
Step 6:
Re-install the diffusor
,
fasten the four retaining screws
,
refit the cover and fasten the screw that
was removed in
step 1.
Step 5:
Mount the base to the desired location by using the supplied screws, washers and o-rings in
each mounting hole
.
At the end of their useful life the packaging and product
should be disposed of via a suitable recycling centre.
Do not dispose of with your normal household waste.
Do not burn.
The light source contained in this luminary shall only be replaced by the manufacturer, or his
agent, or a similar qualified person.