Honeywell satronic DMG 971 Installation Instructions And Maintenance Download Page 1

1

A Honeywell Company

certified Qualitysystem

ISO 9001 / EN 29001

Reg. Nr. 10529

INTRODUCTION

The burner control box DMG 971 controls and supervises
power burner for gas and dual fuel. The control box is
approved and certified according the relevant European
standards. The use on direct air heaters according DIN 4794
is also possible.
The microprocessor- based programming sequence ensu-
res extremely stable timings independent of voltage varia-
tions, ambient temperature and/or switch-on cycles. The
built-in information system not only provides a continuous
monitoring of the actual state of the box (very helpful es-
pecially for monitoring the start-up phase) but also informs
about the cause of a possible lock out. The lock out cause
is stored in such a way that it can be retrieved even after a
power failure.
The control box is designed for maximum safety in case of
fluctuations in the voltage supply. If the mains voltage drops
below the permitted level, operation is interrupted and the
control box automatically prevents the start sequence from
being repeated. In this way, the safety of the system is not
put at risk by a drop in the mains voltage. This low-voltage
protection works not only during start-up but also perma-
nently during operation.

CONSTRUCTIONAL FEATURES

Microprocessor, electronic components, output relais and
flame amplifier are placed on two printed circuit boards.
These plus the lockout- and reset circuit are well protected
inside a flame resistant, plug-in type plastic housing.
The reset switch for reset / remote lockout with its built-in
LED for displaying the information system plus the central
fixing screw are placed on top of the housing.
The wiring base S98 is equipped with spare- and
extraterminals and allows together with  a variety of cable
entry points utmost flexibility of electrical wiring.

The DMG 971 is funstionally compatible to MMI 811 and
MMI 811.1

Please note: Is the DMG 971 to be used to
replace the MMI 811 or 811.1, care has to be
taken to make sure the air proving switch (LW) is
wired between terminals 4 and 7 and not like on
the MMI between 5 and 7.

DMG 971

Gas Burner Safety Control

For 2-stage forced draught and combi
oil/gas burners

Possible flame detectors:
- Ionisation probe
- Infrared flicker detector 1020
- UV flame sensor UVD 971

TECHNICAL DATA

Operating voltage

220 / 240 V (-15... +10%)
50 Hz ( 

±

5%)

Fuse rating

10 A fast, 6 A slow

Power consumption

ca. 15 VA

Max. load per output
- term. 3 ignition trafo

1.5 A, cos 

ϕ

 0.2

- term. 4 motor

2.0 A, cos 

ϕ

 0.4

- term. 5 + 6 solenoid valves

1.0 A, cos 

ϕ

 0.4

- term. B alarm indicator

1.0 A, cos 

ϕ

 0.4

total load

5.0 A, cos 

ϕ

 0.4

max. 10 A during 0.5 sec

Air proving switch

1 working contact 4 A, 230V

Stray light monitoring

5 sec

Sensitivity (operation)

µ

A

Min. required ion. current

1.5 

µ

A

Sensitivity for stray light

0.4

µ

A

Ionisation probe insulation

Probe - earth
greater than 50 M

stray capacity

Probe - earth
less than 1000 pF

cable lenght

< 3 m

Flame detectors

IRD 1020

side-on or end-on viewing

UVD 971

end-on viewing

Weight incl. Wiring base

190 g

Mounting position

any

Protection class

IP 40

Approved ambient parameter
for control and flame detector

max. 95% at 30

°

 C

- for operation

-20

°

 C... +60

°

 C

- for storage

-20

°

 C... +80

°

 C

Build-up of ice, penetration of water and condensing
water are inadmissible
Approvals according
to European standards

EN 298 and EN 230, as
well as all other relevant
Directives and standards

Classified acc. to EN 298

FTLLXN

Timings (sec.)

0737.11-00-e/01/99

  Model

waiting time

max. reaction time for

supervised

pre-ignition

ignition time

Stray light

safety time

delay

start

air proving switch

pre-purge time

time

total

monitoring

2nd-stage

tlw

tv1

tvz

tz

tf

ts

tv2

01

0

60

24

3

5

5

3

12.5

Summary of Contents for satronic DMG 971

Page 1: ...nd allows together with a variety of cable entry points utmost flexibility of electrical wiring The DMG 971 is funstionally compatible to MMI 811 and MMI 811 1 Please note Is the DMG 971 to be used to replace the MMI 811 or 811 1 care has to be taken to make sure the air proving switch LW is wired between terminals 4 and 7 and not like on the MMI between 5 and 7 DMG 971 Gas Burner Safety Control F...

Page 2: ...lse short pause _ long pause 1 2 Lock out diagnoses In case of a failure the LED is permanently illuminated Every 10 seconds the illumination is interrupted by a flash code whichindicatesthecauseoftheerror Thereforethefollowing sequence is performed which is repeated as long as the unit is not reset Sequence illuminated phase dark phase Flash Code dark phase for 10 sec for 0 6 sec for 1 2 sec Erro...

Page 3: ...t mode If the voltage rises again the controlboxperformsautomaticallyastart upassoonasthe mains voltage is 187 Veff 5 Safety The design and control sequence of the DMG 971 controls will comply with the currently applicable standards and regulations see also TECHNICAL DATA 6 Mounting and electrical wiring Wiring base 3 earth terminals with additional terminal for burner earthing 3 neutral terminals...

Page 4: ...d lockout appears if the air proving switch LW contact is still in it s closed position e g welded contacts Has the air proving switch LW changed to it s open position in the meantime e g by a run down motor a normal start sequence follows 3 Fault finding The built in information system facilitates the trouble shoot ing in the case of problems occurring during start up or during operation A list o...

Page 5: ...t stage V2 Solenoid valve 2nd stage LW Air proving switch SA External lock out signal tlw max reaction time for air proving switch tv1 Supervised pre purge time tvz Pre ignition time tz Ignition time total ts Safety time tv2 Delay 2nd stage M Ph N HS ST GW RT EV IS Z V1 V2 SA LW 1 2 3 4 5 6 7 8 9 C A B SV tvz tz ts tv2 tw tv1 tlw rv1 rs 2 6 5 7 4 3 C 9 B 8 1 A rz rv2 Flame amplifier Reset µC Reset...

Page 6: ...2 Support for IRD Holder M93 for IRD 1020 59093 Support for UVD Holder M74 for UVD 59074 Connection cable Plug type 3 core cable 0 6 m with tag wire ends 7236001 The above ordering information refers to the standard version Special versions are also included in our product range Specifications subject to change without notice VARIATION IRD right HOLDER M 93 FOR IRD left axial 35 3 14 4 5 26 15 1 4...