Honeywell RM7800E Installation Instructions Manual Download Page 1

INSTALLATION INSTRUCTIONS

66-1085-04

SIL

3

Capable

RM7800E,G,L,M; RM7840E,G,L,M

7800 SERIES Relay Modules

APPLICATION

The Honeywell RM7800/RM7840 Relay Modules are 

microprocessor-based integrated burner controls for 

automatically fired gas, oil, or combination fuel single burner 

applications. The RM7800/RM7840 Relay Modules are used 

for UL/CSA On/Off, UL/CSA Modulating, and FM/IRI 

Modulating burner applications. The RM7800/RM7840 system 

consists of a Relay Module. Keyboard Display Modules 

(standard with RM7800), Dust Cover (standard with RM7840), 

Subbase, Amplifier, and Purge Card. Options include DATA 

CONTROLBUS MODULE™, Remote Display Mounting, First-

Out Expanded Annunciator and Communications through 

Modbus™.

Functions provided by the RM7800/RM7840 include 

automatic burner sequencing, flame supervision, system 

status indication, system or self-diagnostics and 

troubleshooting. The RM7800/RM7840 is a solid state 

replacement for the electromechanical R4140 Automatic 

Programming Control.

This document provides installation and static checkout 

instructions. Other applicable publications are:

65-0084:Q7800A,B 22-Terminal Wiring Subbase Product 

Data.

65-0089:ST7800A Plug-In Purge Timer Installation 

Instructions.

65-0090:S7800A Keyboard Display Module Product Data.

65-0091:S7810A Data ControlBus Module™ Product Data.

65-0095:S7820 Remote Reset Module Product Data.

65-0097:221729C Dust Cover Packing Sheet.

65-0101:S7830 Expanded Annunciator Product Data.

65-0109:R7824, R7847, R7848, R7849, R7851, R7852, 

R7861, R7886 Flame Amplifiers for the 7800 SERIES 

Product Data.

65-0131:221818A Extension Cable Assembly Product 

Data.

65-0229:7800 SERIES RELAY MODULES Checkout and 

Troubleshooting Product Data.

65-0249:S7810M ModBus™ Module Product Data.

SPECIFICATIONS

Electrical Ratings, see Table 3:

Voltage and Frequency: 120 Vac (+10/-15%), 50 or 60 Hz 

(±10%).

Power Dissipation: RM7800/RM7840: 10W maximum.

Maximum Total Connected Load: 2000 VA.

Fusing: 15A maximum, Type SC or equivalent Fast Blow.

Environmental Ratings:

Ambient Temperature:

Operating: -40°F to +140°F (-40°C to +60°C).

Storage: -40°F to +150°F (-40°C to +66°C).

Humidity: 85% relative humidity continuous, noncondensing.

Vibration: 0.5G environment.

SIL 3 Capable:

SIL 3 Capable in a properly designed Safety Instrumented 

System. See form number 65-0312 for Certificate Agree-

ment.

Approvals:

Underwriters Laboratories Inc. Listed: File No. MP268, 

Guide No. MCCZ.

Canadian Standards Association Certified: LR9S329-3.

Factory Mutual Approved: Report No. J.I.1V9A0.AF. 

Swiss Re (formerly IRI): Acceptable.

Federal Communications Commission, Part 15, 

Class B—Emissions.

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 

them could damage the product or cause a hazardous 

condition.

2.

Check the ratings given in the instructions and marked 

on the product to make sure the product is suitable for 

the application.

3.

Installer must be a trained, experienced, flame 

safeguard service technician.

4.

After installation is complete, check out the product 

operation as provided in these instructions.

WARNING

Fire or Explosion Hazard. 

Can cause property damage, severe injury, 

or death.

To prevent possible hazardous burner operation, verify 

safety requirements each time a control is installed on 

a burner. 

Summary of Contents for RM7800E

Page 1: ...Amplifiers for the 7800 SERIES Product Data 65 0131 221818A Extension Cable Assembly Product Data 65 0229 7800 SERIES RELAY MODULES Checkout and Troubleshooting Product Data 65 0249 S7810M ModBus Module Product Data SPECIFICATIONS Electrical Ratings see Table 3 Voltage and Frequency 120 Vac 10 15 50 or 60 Hz 10 Power Dissipation RM7800 RM7840 10W maximum Maximum Total Connected Load 2000 VA Fusing...

Page 2: ...ty shutdown Vibration Do not install the relay module where it could be subjected to vibration in excess of 0 5G continuous maximum vibration Weather The relay module is not designed to be weather tight When installed outdoors protect the relay module using an approved weather tight enclosure Mounting Wiring Subbase 1 Mount the subbase in any position except horizontally with the bifurcated contac...

Page 3: ...us Module cable length depends on the number of system modules connected the noise conditions and the cable used The maximum length of all Data Controlbus Module interconnecting wire is 1000 feet 10 Make sure loads do not exceed the terminal ratings Refer to the label on the RM7800 RM7840 or to the ratings in Tables 3 4 and 5 Final Wiring Check 1 Check the power supply circuit The voltage and freq...

Page 4: ...IFIER RELAY DRIVE CIRCUIT CONTROL POWER TEST JACK REMOTE RESET DDL DDL COMMUNICATIONS INDICATES FEEDBACK SENSING OF RELAY CONTACT STATUS AND LINE VOLT INPUTS FIELD WIRING INTERNAL WIRING IGNITION PILOT PILOT V2 MAIN VALVE 1K 9K RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS LIMITS CONTROLLER RUNNING LOCKOUT INTERLOCK PRE IGNITION INTERLOCK 1K1 2K1 5K1 8K1 8K2 9K1 9K2 120 Vac 50 60 Hz FLAME SIGNAL T...

Page 5: ...re 3 Make sure that mechanically tightened joints along the ground path are free of nonconductive coatings and pro tected against corrosion on mating surfaces Signal ground KDM Data ControlBus Module Use the shield of the signal wire to ground the device to the signal ground terminals 3 c of each device Connect the shield at both ends of the chain to earth ground Terminal No Description Ratings G ...

Page 6: ... both sides of the RM7800 RM7840 for electrical signal voltage probes 3 Make sure no subbase wiring is projecting beyond the terminal blocks Tuck in wiring against the back of the subbase so it does not interfere with the knife blade terminals or bifurcated contacts IMPORTANT The RM7800 RM7840 must be installed with a plug in motion rather than a hinge action 4 Mount the RM7800 RM7840 by aligning ...

Page 7: ...OR DOES NOT START UNTIL THE HIGH FIRE SWITCH MAKES RM7800L1053 RM7840L1026 TERMINAL 21 PROVIDES INTERMITTENT PILOT FUNCTION 1 2 2 1 1 TIMED PREPURGE POWER FLAME MAIN PILOT ALARM POWER FLAME MAIN PILOT ALARM ALARM ALARM ALARM 00 IC PII SSC LED DISPLAY M12261C G L2 3 4 4 5 5 6 7 8 9 10 F L1 13 14 15 16 17 18 19 20 21 22 12 LOCKOUT INTERLOCKS INC AIR FLOW SWITCH MASTER SWITCH LOW FIRE START SWITCH 5 ...

Page 8: ...TION TRANSFORMER 2ND STAGE FUEL VALVE OPTIONAL R W B R W B L1 HOT L2 1 21 9 10 1ST STAGE FUEL VALVE L2 Q7800 3 15 OR 30 SEC INTERRUPTED INTERMITTENT PILOT VALVE 2 2 1 3 4 4 4 JUMPER WIRE FOR 30s MFEP RM7800G RM7840G POWER OPERATING CONTROLS AND INTERLOCKS BURNER FLAME SIGNAL FIRING RATE MOTOR INITIATE INITIAL POWERUP ONLY POWER STANDBY PREPURGE HOLD DRIVE TO LOW FIRE POWER PILOT FLAME MAIN POWER P...

Page 9: ...ON TRANSFORMER 2ND STAGE FUEL VALVE OPTIONAL L1 HOT L2 1 21 9 10 1ST STAGE FUEL VALVE L2 Q7800 3 INTERMITTENT PILOT 2 1 3 4 4 RUNNING INTERLOCKS INC AIR FLOW SWITCH 2 2 2 DAMPER MOTOR RM7800M RM7840M POWER OPERATING CONTROLS AND INTERLOCKS BURNER FLAME SIGNAL DAMPER MOTOR INITIATE INITIAL POWERUP ONLY POWER STANDBY PREPURGE HOLD DRIVE TO LOW FIRE POWER PILOT FLAME MAIN POWER PFEP 10 SEC 4 SEC IF J...

Page 10: ...ed f Internal system fault occurred g Purge card is not installed or is removed h Purge card is bad 3 PREPURGE Period a Preignition Interlock opens anytime during PREPURGE period RM7840E L b Flame signal is detected after first ten seconds during PREPURGE RM7840E L c High Fire Switch fails to close within four minutes and fifteen seconds after the firing rate motor is commanded to drive to the hig...

Page 11: ...met the INITIATE sequence restarts If the condition is not corrected and the hold condition exists for four minutes the RM7800 RM7840 locks out Causes for hold conditions in the INITIATE sequence a AC line dropout is detected b AC line noise prevents a sufficient reading of the line voltage inputs c Low line voltage brownouts occur The INITIATE sequence also delays the burner motor starter from be...

Page 12: ...he RM7800 RM7840 is now in RUN and remains in RUN until the controller input terminal 6 opens indicating that the demand is satisfied or a limit opened Postpurge The RM7800 RM7840 provides a fifteen second POSTPURGE following the completion of the RUN period The blower motor output is powered to drive all products of combustion and any unburned fuel from the combustion chamber It also supplies com...

Page 13: ...ch when placed in the TEST position holds in PREPURGE with the firing rate motor in the High Fire position 2 In the measured PREPURGE sequence the Run Test Switch when placed in the TEST position causes the PREPURGE timing to stop The firing rate motor is in the High Fire position 3 In Prepurge Drive to Low Fire position the Run Test Switch when placed in the TEST position holds the burner sequenc...

Page 14: ...ty set on the 0 300 Vac scale 2 Two jumper wires no 14 wire insulated 12 inches 304 8 mm long with insulated alligator clips at both ends An ammeter may be used in place of a jumper wire to check the amp usage when testing the blower motor ignition pilot and main valve operation General Instructions 1 Perform all applicable tests listed in Static Checkout Table 8 in the order listed 2 Make sure al...

Page 15: ...ons to Terminal 8 If using direct spark ignition check the first stage fuel valve s instead of the pilot valve Same as test no 6 If using direct spark ignition check the first stage fuel valve s instead of the pilot valve 8 4 9 Automatic main fuel valve s open If using direct spark ignition on a model with intermittent pilot on Terminal 21 check the optional second stage fuel valve if used 1 Liste...

Page 16: ... motor is used motor drives open line voltage at Terminal 18 after motor is in Low Fire position 1 Low Fire Start Switch 2 Damper motor 17 RM7800M RM7840M with open damper contacts 4 5 and 4 13 18 L2 If damper motor is used motor drives open zero volts at Terminal 18 1 Low Fire Start Switch 2 Damper motor Final All CAUTION Equipment Damage Hazard Improper wiring can damage equipment On completing ...