R8184M PROTECTORELAY

OIL BURNER CONTROL

APPLICATION

The R8184M Protectorelay control provides automatic,

nonrecycling control of combination oil burner heating and
cooling systems when used with a C554A Cadmium Sulfide
(cad cell) Flame Detector and low voltage thermostat. It
includes a 40 VA transformer to power a cooling contactor
and fan relay during the cooling operation.

ELECTRICAL RATINGS:

Load Relay Contact Ratings:

Full Load: 7.4A
Locked Rotor: 44.4A

Transformer:

Primary Voltage: 120V, 60 Hz.
Secondary Voltage: 26.5V, 60 Hz.

Ignition Rating: 360 VA in addition to the load relay contact

rating.

Power Consumption:

Start: 9.0A
Running: 5.5A

INSTALLATION

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to follow them

could damage the product or cause a hazardous condition.

2. Check the ratings given in these instructions and on the

product to ensure the product is suitable for your application.

3. Ensure the installer is a trained, experienced service

technician.

4. After completing installation, use these instructions to

check product operation.

Fig. 1—Wiring diagram of R8184M.

CHOOSE LOCATION

Mount the R8184M on a 4 x 4 inch junction box, directly
on the burner housing, or inside the appliance cabinet.

In replacement applications, mount the R8184M in the
same location as the old control.

Make all line voltage connections in a wiring enclosure
such as a junction box or the appliance wiring compart-
ment.

Ensure operating temperatures at the selected loca-
tion are between -40

°

 F and 130

°

 

F [-40

°

 C and 54

°

 C].

MAKE WIRING CONNECTIONS AND MOUNT R8184M

1. Ensure all wiring complies with local codes and ordi-

nances.

2. Make line voltage connections as shown in Fig. 1.

Splice leads with solderless connectors.

Do not exceed load ratings shown on device label.

Leave enough slack in the wires to permit easy
access into the junction box.

3. Mount the R8184M to the junction box. Refer to Fig. 2.
4. Connect the C554A Cadmium Sulfide Cell (ordered

separately) leadwires to the F-F terminals on the terminal
strip.

5. Connect all remaining low voltage wiring connections

as shown in Fig. 1.

NOTE: Y and G terminals are provided to simplify connec-

tions of cooling equipment; they are not connected to the
internal circuitry of the R8184M.

M1559

1 USED FOR 4 AMP THERMOSTAT ONLY.

CAD 
CELL

F

R

W

Y

THERMOSTAT

G

FAN RELAY

COOLING 
CONTACTOR

W

C

R

Y

F

G

(T)

(T)

R8184M PROTECTORELAY 
CONTROL

K1

SS

SAFETY 
SWITCH 
HEATER

R4

1K1

BLUE

RED

BROWN

TRIAC

BILATERAL 
SWITCH

CAPACITOR

R2

R1

LOCKOUT 
INDICATOR 
LIGHT

SS

1K2

BLACK

WHITE

ORANGE

BLACK

JUNCTION 
BOX

IGNITION

OIL VALVE

BURNER

LIMIT

L1 
(HOT)

L2

1

Reviews: