Honeywell QX Series Installation Instruction Download Page 1

 

QX Recorders - Installation Instruction 

 
Portable Case 

 

 

QX Recorder 

 

 

 

 

This Installation Instruction sheet is intended as a guide for replacing or installing hardware and for setting up 
functionality in the recorder. Refer to the User manual for detailed operational requirements.   
The QX recorders are designed for ease of assembly with minimal disturbance to the rest of the unit. If unsure, please 
return the unit to your supplier for repair or upgrade. 
Removing the case and opening the back of the recorder should only be performed under the following circumstances: 
When an item of hardware requires individual replacement. 
When an item of hardware is to be retrospectively fitted. 
In all other instances it is recommended that the complete unit be returned to an authorised agent or service centre. 
For Agency Approved recorders the product needs to be upgraded or repaired by an Authorized Repair facility 

 

 

 WARNING 

HAZARDOUS VOLTAGES  

Disconnect all power to the recorder before removing the case and attempting any maintenance procedures. 

SAFETY TESTS 

Upon completion of service procedures detailed in this manual two basic safety tests should be performed in order to 
ensure continued safe operation of the instrument. 
Earth Resistance; 25 VDC applied between case and protective earth, bonding resistance should be < 0.1 Ohm. 
Insulation Resistance; 500Vdc applied between the earth terminal, and the live and neutral terminal shorted together, 
insulation resistance to be >2.0 MOhm. (Mega Ohm, NOT milli Ohm) 

Failure to comply with these instructions could result in death or serious injury

 

 

 CAUTION 

OBSERVE ANTI-STATIC PRECAUTIONS 

Refer to BS EN61340-5-1: 2001. Basic specification. Protection of electrostatic sensitive devices. 
Full anti-static precautions MUST be observed when in contact with the electronics of your recorder. 

SAVE DATA, SETUPS AND LAYOUTS 

Removal of PCBs and battery back-up will result in the loss of all non-volatile data.  
Ensure all data and set-ups are saved. 

Failure to comply with these instructions may result in product damage.

 

 
 

43-TV-33-62 iss.1   GLO   Oct 06  UK 

 

 

Summary of Contents for QX Series

Page 1: ...nnect all power to the recorder before removing the case and attempting any maintenance procedures SAFETY TESTS Upon completion of service procedures detailed in this manual two basic safety tests should be performed in order to ensure continued safe operation of the instrument Earth Resistance 25 VDC applied between case and protective earth bonding resistance should be 0 1 Ohm Insulation Resista...

Page 2: ...on the work surface without getting scratched or damaged Fitting the Portable case Unpack the portable case kit and check all the parts are present See fig 1 Terminal cover New Case 43 TV 33 62 iss 1 GLO Oct 06 UK 2 Fig 1 M3x6 screws Handle fixing covers 2 Handle fixings 2 Handle inner and cover Rubber feet Handle fixing screws 2 Handle fixing nuts 2 ...

Page 3: ... handle Place it on the case and align the holes See fig 2 Fig 2 Place one of the handle fixing screws through the fixing through the handle and through the case On the inside of the case fit one of the handle fixing nuts with integral washer Leave nut loose Fix the other end of the handle in the same way When both ends are fixed tighten the nuts until the screw thread is flush with the back of th...

Page 4: ... 5 Fig 4 Clip cover under front edge Push cover down to clip in place Turn the case upside down and attach the 4 self adhesive feet in the positions shown in Fig 6 below Fig 6 To remove the existing case from the recorder remove the 4 M3 screws 2 in each side 43 TV 33 62 iss 1 GLO Oct 06 UK 4 ...

Page 5: ...r of the recorder Ensure the case is orientated with the handle on the top of the recorder Slide the case fully forward ensuring that no internal cables get trapped between the case and front bezel The case should sit flat on the back of the front bezel Re fit the four M3 screws in the sides of the case Fig 8 Re fit the 4 screws in the portable case Remove the rear panel from the old case by remov...

Page 6: ...el on the new case angle the rear panel as shown to line up two location points with the floor of the recorder s case Fig 9 Re fit the M3 screw in the top right hand corner See Fig 10 Fig 10 43 TV 33 62 iss 1 GLO Oct 06 UK 6 ...

Page 7: ... have been made to the back of the recorder To fit the terminal cover align the cover with the back of the recorder and fit the top left hand screw which holds the terminal cover rear panel and case together See Fig 11 Fig 11 43 TV 33 62 iss 1 GLO Oct 06 UK 7 Turn the recorder on its side and fit the bottom terminal cover fixing screw Fig 12 Fig 12 Fit M3 screw Fit M3 screw Copyrighted Materials F...

Reviews: