PW6K1R1E Wiring and Setup
Status LEDs
PW6K1R1E Configuration and Installation Guide
,
Document
800-07986V1, Revision A
11
•
When you are momentarily removing power to unlock the door, as with a
mag lock, the
Normally Closed and Common
poles are used.
Check with local building codes for proper egress door installation.
Caution:
Door lock mechanisms can generate feedback to the relay circuit which can
cause damage and premature failure of the relay. For this reason, it is recommended
that you should use either a diode or MOV (metal oxide varistor) to protect the relay.
Wire should be of sufficient gauge to avoid voltage loss.
Figure 2-7: Relay Circuit Wiring Diagram
Note:
The initial charge of the battery may take up to 24 hours to be fully charged.
2.10 Status LEDs
At power-up
,
LEDs 2 through 6 are turned ON then OFF in sequence.
After the above sequence has completed successfully, the PW6K1R1E goes to the
“waiting for IP address” mode.
Diode Selection:
• Diode current rating: 1x
strike count
• Diode breakdown voltage:
4x strike voltage
• For 12VDC or 24VDC
strike, diode 1N4002
(100V/1A) typical
MOV Selection:
• Clamp voltage: 1.5x VAC
RMS
• For 24VAC strike,
Panasonic ERZ-
C07DK470 typical
+
-
TB6
2-C
NC
NC
NO
1
NO
1-C
O
TB6
1
NO
1-C
NC
NC
NO
2-C
LED
DESCRIPTION
1
Off-line: Off-line = 0.2 second ON, 0.8 second OFF
2
Waiting for IP address: 0.5 second ON, 0.5 second OFF
3
Flashes when data is received from either reader
4
Input IN1 Status: OFF = Inactive, ON = Active, Flashing = Trouble