PW-6000 Installation
System Configuration via Web Interface
3.8 Memory and Real Time Clock Backup Battery
The event log buffer and the real time clock are backed up by a 3V lithium battery.
This BR2325, BR2330, or CR2330 battery should be replaced annually. A
replacement battery may be obtained from Honeywell or a local battery retailer.
However, the replacement battery must be UL recognized.
Warning:
Battery may explode if mistreated. DO NOT RECHARGE, DISASSEMBLE
or DISPOSE OF IN FIRE!
AVERTISSEMENT:
La batterie peut éclater si elle est maltraitée. NE PAS
RECHARGER, DEMONTER OU JETER AU FEU!
4 System Configuration via Web Interface
The PW-6000 comes with
Access Control Device Server Manager (ACDSM)
. The
ACDSM is a built-in web server, through which you can configure network and other
system settings.
Notes:
• If you are using Internet Explorer Enhanced Security Configuration, you
cannot access the ACDSM web server. All pages will display “Bad Request!”
You must uninstall the Enhanced Security option before you can access the
ACDSM.
• The default factory-set TCP/IP address for the built-in system configuration
web server is
192.168.0.251
4.1 Connecting to ACDSM for the First Time
1. Use the factory default controller IP address
192.168.0.251
.
2. Set the DIP switches to
S4=OFF
,
S3=OFF
,
S2=ON
,
S1=OFF
.
Note:
S1 must be set to OFF for the factory default. After the panel powers up,
change S1 to ON to enable the use of the default user name and password.
3. Connect the computer to host the web server via Ethernet
Port 0
. Connection
should be via crossover Ethernet cable or by the regular Ethernet cables
connected via the hub.
4. Set the host computer to the static IP address
192.168.0.250
to be able to
connect to the factory-default PW-6000 controller at address
192.168.0.251
.
5. Power up the PW-6000 controller.