Installing the PRO3200 Two-Reader Module
Specifications
Specifications
The Two-Reader Module is for use in low voltage, class 2 circuits only.
Primary power
:
• 10 to 14VDC 650mA maximum
• 12VDC @ 200mA nominal (plus reader current)
Relay contacts
:
• Relays 0 and 2 outputs, Form-C, 5A @ 28VDC, inductive
• Relays 1, 3, 4, and 5 outputs, Form-C, 2A @ 28VDC, resistive
Inputs
:
• 8 supervised, End of Line resistors 1k ohm ± 1% tolerance
• 2 unsupervised dedicated inputs
Reader interface:
Communication
:
Wire requirements
:
Mechanical
:
Environment
:
Reader power
5VDC(5 - 6.2) 150mA max. each or 12VDC (pass-through), 175mA
max. each
Reader LED output
TTL compatible, high > 3V, low < 0.5V, 5mA source/sink max.
Reader buzzer output Open collector, 5VDC open circuit max. 10mA sink max.
Reader data inputs
TTL compatible inputs
RS-485
9,600 to 38,400 bps
Power
1 twisted pair, 18AWG
RS-485
24AWG, 4,000 feet (1,200 m) max., 2-twisted pair with shield (120
,
23pf) (Belden 9842 or equiv.)
Inputs
1 twisted pair per input, 30 ohms max.
Outputs
As required for the load
Readers
6 conductors, 18AWG, 500 feet (150m) max. shield and drain
Dimension
5.5" (140mm) W x 9" (229mm) L x 1" (25mm) H
Weight
12 oz. (340g) nominal
Temperature
0°C to +49°C, operating, -55°C to +85°C, storage
Humidity
0% to 85% RHNC