Honeywell P7640A Installation Instructions Download Page 1

INSTALLATION INSTRUCTIONS

62-0210-07

P7640A,B 

Differential Pressure Sensors

APPLICATION

The P7640A Panel Mount and P7640B Duct Mount 

Differential Pressure Sensors provide reliable, accurate 

measurement and control. Proper applications include 

measurement of extremely low pressure applications such 

as: building/room pressure, air flow, variable air volume, 

filter status, and duct pressure. They are ideal for clean 

rooms, hospitals, fume hoods, and computer rooms.

The P7640 Pressure Sensors are designed with field-

selectable 4-20 mA, 0-5 Vdc, or 0-10 Vdc output. The four 

pressure ranges fall between 0–1 in. w.c./0–250 Pa or 0–

10 in. w.c./0–2500 Pa, depending on the model.

Accessory

32003169-001 Duct Pressure Pick-up Probe, 4 in.

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 

them could damage the product or cause a hazard-

ous condition.

2.

Check ratings given in instructions and on the 

product to ensure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

IMPORTANT

All wiring must agree with applicable codes, 

ordinances and regulations.

Mounting

Screw holes are accessed inside the enclosure (with the 

cover removed) and are located in the upper left and 

lower right corners.

Panel Mount

Run tubing from one (static) or both (differential) barb 

fittings, making sure the typically higher pressure source 

is connected to the port labeled HI, and the typically 

lower pressure source is connected to the port labeled 

LO.

Duct Mount

The units with the integral probe should typically be 

mounted at the high pressure location when used for 

differential control.

CONFIGURATION

Select the proper output, mode, and pressure range 

using the switches and jumpers:

1.

Select output using the output switch:

a. Current: mA (then skip to step 3), or

b. Voltage: Volt.

2.

Select 0-10 Vdc or 0-5 Vdc using jumper J4.

3.

Select bi- or uni-directional mode using jumper J5.

NOTE: Setting for 0 to 1 in. w.c. and bi-directional 

will give output from -1.0 to 1.0 in. w.c.

4.

Select inches w.c. or Pascal scale using jumper J7.

5.

Select fast or standard response time using jumper 

J8.

6.

Select appropriate full-scale pressure range using 

the rotary switch. Align arrow (not the slot) to the 

desired range. See Table 2 for the range selection 

guide.

NOTE: Note that either the 1 in. w.c. or 10 in. w.c. 

scale is marked. This is the available 

scale for that given model. When the 

range is changed, the LCD models 

momentarily indicate selected range.

7.

Set output according to Table 1.

Table 1. Controller Compatibility 

and Output Settings.

Controller

Required Sensor

 Output Setting

L

ON

S

PEC

Setting

W7750, W7760, W7761

4-20 mA

FilterPress or 

P7610B

W7750B, W7760C, 

W7753, W7760

0-10 Vdc (default)

FilterPress or 

P7610F, or voltage

Non-Honeywell

0-5 Vdc

n/a

Summary of Contents for P7640A

Page 1: ...r left and lower right corners Panel Mount Run tubing from one static or both differential barb fittings making sure the typically higher pressure source is connected to the port labeled HI and the typically lower pressure source is connected to the port labeled LO Duct Mount The units with the integral probe should typically be mounted at the high pressure location when used for differential cont...

Page 2: ...WR OUT COM ZERO RESPONSE FAST STD mA VOLT OUTPUT JP8 UNITS IN W C PA JP7 MODE BI UNI JP5 VOLT SV 10V JP4 7 1 2 3 4 5 6 M27291 12 TO 30 Vdc POWER SUPPLY CONTROLLER METER OR RECORDER INPUT SIGNAL COMMON M27292 ZERO PWR OUT COM ZERO RESPONSE FAST STD mA VOLT 1 DRY CONTACT TO AUTOMATICALLY ZERO THE SENSOR UPON CLOSURE OPTIONAL 1 OUTPUT JP8 UNITS IN W C PA JP7 MODE BI UNI JP5 VOLT SV 10V JP4 7 1 2 3 4 ...

Page 3: ...exposed to the same pressure Zeroing the device automatically resets the output and displays zero pressure To do this either Press and hold the ZERO pushbutton for 2 seconds or Provide contact closure on the ZERO terminals To ensure this place a piece of jumper tubing between HI and LO NOTE To avoid accidental zero this feature is enabled only while detected pressure is within 5 of factory calibra...

Page 4: ...t Damage Hazard Can damage the device beyond repair Disconnect power supply before installation NOTE Wiring to the ZERO terminals is optional Fig 4 Wiring for voltage Vdc output Fig 5 Wiring for current mA output LonSpec is a trademark of Echelon Corporation L1 L2 CONTROLLER METER OR RECORDER INPUT SIGNAL COMMON ZERO PWR OUT COM ZERO RANGE mA VOLT VOLT 5V 10V MODE BI UNI 10 1 10 5 2 5 1 0 1 0 5 25...